Operating menu
Switch-on delay
Navigation
Prerequisite
Description
User entry
Factory setting
Switch-off value
Navigation
Prerequisite
Description
User entry
Factory setting
Additional information
208
A
Switch-on value
B
Switch-off value
C
Output closed (conductive)
D
Output opened (non-conductive)
Setup → Advanced setup → Switch output → Switch-on delay
• Switch output function (→ 205) = Limit
• Assign limit (→ 206) ≠ Off
Define switch-on delay.
0.0 to 100.0 s
0.0 s
Setup → Advanced setup → Switch output → Switch-off value
Switch output function (→ 205) = Limit
Enter measured value for the switch-off point.
Signed floating-point number
0
The switching behavior depends on the relative position of the Switch-on value and
Switch-off value parameters; description: see the Switch-on value parameter
(→ 207).
Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
B
A
t
C
D
t
A0015586
Endress+Hauser