Levelflex FMP51, FMP52, FMP54 FOUNDATION Fieldbus
Level (Manual)
Navigation
Prerequisite
Description
User entry
Factory setting
Level (Semiautomatic)
Navigation
Prerequisite
Description
Customer value
Navigation
Prerequisite
Description
User entry
Factory setting
Activate table
Navigation
Prerequisite
Description
Selection
Endress+Hauser
Setup → Advanced setup → Linearization → Level
• Linearization type (→ 191) = Table
• Table mode (→ 195) = Manual
Enter level value of the table point (value before linearization).
Signed floating-point number
0 %
Setup → Advanced setup → Linearization → Level
• Linearization type (→ 191) = Table
• Table mode (→ 195) = Semiautomatic
Displays measured level (value before linearization). This value is transmitted to the table.
Setup → Advanced setup → Linearization → Customer value
Linearization type (→ 191) = Table
Enter linearized value for the table point.
Signed floating-point number
0 %
Setup → Advanced setup → Linearization → Activate table
Linearization type (→ 191) = Table
Activate (enable) or deactivate (disable) the linearization table.
• Disable
• Enable
Operating menu
197