11
PROCEDURE FOR WRITING PROGRAM TO CPU
MODULE
End
11
11.1 Basic Model QCPU
- 5
11.1.3 Procedure for writing program
1)
NO
Use the device
initial value?
YES
Set the device memory.
Set the device initial value range.
In the PLC file setting of the PLC
parameter dialog box, set the device
initial value to "Use"
Connect the personal computer, which is
installed with GX Developer, to the CPU
module.
Set the RUN/STOP/RESET switch to the
STOP position, and power ON the PLC
(the ERR. LED turns on).
Choose [Online]
[Format PLC memory]
on GX Deveoper, and format the program
memory or standard RAM.
Choose [Online]
[Write to PLC] on GX
Deveoper, select "Program memory",
and write the parameters, created
program and device initial values to the
program memory.
Power the PLC OFF and then ON, or
reset the CPU module.
Set the RUN/STOP/RESET switch to
the RUN position to place the CPU
module in the RUN status.
NO
Is the ERR. LED
of the CPU module
on (flickering)?
YES
Choose [Diagnosis]
[System monitor]
on GX Developer or perform PLC
diagnosis to check the error factor, and
remove the error factor.
NO
Is boot run
executed?
YES
To Section 11.1.4
Diagram 11.2 Flowchart for writing program