8
PARAMETERS
Item
Parameter No.
Base
model
name
Power
model
name
Basic
0401
setting
Extension
cable
Slots
Switch setting
0407
Error time
output
0403
mode
Hardware
error time
PLC
4004
operation
mode
Detail
setting
I/O
response
0405
time
Control
0406
PLC
8
8.1 PLC Parameters
- 10
8.1.1 Basic model QCPU
Table8.8 I/O assignment list (Continued)
Description
Set the model name of the used
main base unit or extension base
unit. (User memo. Not used for
the CPU module.)
Set the model name of the
power supply module mounted
on the main base unit or
extension base unit. (User
memo. Not used for the CPU
H
module.)
Set the extension cable model
name. (User memo. Not used for
the CPU module.)
Set the number of slots of the
main base unit or extension base
unit.
Set the number of slots for all
base units.
Set various switches of the
H
intelligent function module.
Set whether the output will be
cleared or held when the control
H
CPU results in a stop error.
Set whether the control CPU will
stop or continue operation when
the hardware fault of the
H
intelligent function module
occurs.
Set the response time of the
input module, high-speed input
H
module, hybrid I/O module or
interrupt module.
Set the control CPU of the I/O
module and intelligent function
H
module.
Setting range
16 characters
16 characters
16 characters
2,3,5,8,10,12
Refer to the manual of the used
intelligent function module.
Clear/Hold
Stop/Continue
• Input, hybrid I/O : 1ms, 5ms,
10ms, 20ms, 70ms
• High-speed input, interrupt :
0.1ms, 0.2ms, 0.4ms, 0.6ms,
1ms
• No. 1, No. 2, No. 3
Default value
Reference
No setting
No setting
Section 4.4
No setting
No setting
No setting
Section 6.10
Clear
Section 6.8
Stop
Section 6.9
Input, hybrid I/O :
10ms
Section 6.7
High-speed input,
interrupt : 0.2ms
QCPU User's Manual
No. 1
(Multiple CPU
System)

Hide quick links: