8
PARAMETERS
Item
Parameter No.
Interrupt
counter
start No.
System
interrupt
1008
Fixed scan
setting
interval (n :
28 to 31)
Interrupt program/fixed
1008
scan program setting
Module synchronization
100C
(3) PLC file
Item
Parameter No.
Initial device value
1102
8
8.1 PLC Parameters
- 4
8.1.1 Basic model QCPU
Table8.2 PLC system setting list (Continued)
Description
Set the start No. of the interrupt
counters.
H
Set the execution intervals of the
interrupt pointers (I28 to 31).
Set whether an interrupt
program is executed at high
H
speed or not.
Set whether a CPU module
startup is synchronized with an
H
intelligent function module
startup.
St the file used by the CPU module.
Table8.3 PLC file list
Description
Set the device initial value file
H
used by the CPU module.
Setting range
C0 to 13184 (Can be set up to
the number of counter setting
points - 128)
2ms to 1000ms (1ms unit)
Execute at high speed/Do not
execute at high speed
Synchronize/Do not synchronize
with intelligent function module
startup
Diagram 8.3 PLC file
Setting range
• Not used
• Use
Default value
Reference
No setting
Section 9.2.11(4)
I28 : 100ms
I29 : 40ms
Section 9.10
I30 : 20ms
I31 : 10ms
Do not execute at
Section 3.1.3
high speed
Synchronize with
intelligent function
----
module startup
Default value
Reference
Not used
Section 6.26