Mitsubishi Q00JCPU User Manual page 419

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

8
PARAMETERS
(4) PLC RAS
Item
Parameter No.
WDT
(watchdog
WDT
3000
timer)
setting
setting
Computation
error
Expanded
command
error
Fuse blown
Operating
mode when
3002
I/O module
there is an
comparison
error
error
Intelligent
module
program
execution
error
Carry out
battery
check
Carry out
Error check
fuse blown
3001
check
Carry out
I/O module
comparison
Constant scanning
3003
Make the various settings for the RAS function.
Table8.4 PLC RAS list
Description
Set the watchdog timer value of
H
the CPU module.
Set the operation mode of the
H
CPU module at error detection.
Set whether the specified error
H
will be checked or not.
Set the constant scan time.
H
Diagram 8.4 PLC RAS
Setting range
10ms to 2000ms (10ms unit)
200ms
Stop/Continue
Stop
Check/Do not check
Check
1ms to 2000ms (1ms unit)
No setting
8.1 PLC Parameters
8.1.1 Basic model QCPU
Default value
Reference
Section 3.2
Section 6.17
Section 6.17
Section 6.2
8
1
2
3
4
5
6
7
8
- 5