Mitsubishi Q00JCPU User Manual page 385

Q series, logic
Hide thumbs Also See for Q00JCPU:
Table of Contents

Advertisement

6
FUNCTIONS
Table6.40 Processing times related to high speed I/O refresh and high speed buffer transfer
Processing Item
Waiting time
High speed interrupt start high speed
interrupt end
X input
Buffer memory read
I49 overhead
High speed interrupt program
execution
Buffer memory write
Y output
• Max. 37.5 s or more than 37.5 s instruction processing time
• Max. 40 s when MELSECNET/H, CC-Link or intelligent function modules are mounted on
extension base unit.
22 s
<Main base unit>
Time = 0.14
(total number of X points)+0.65
<Extension base unit>
Time = 0.21
(total number of X points)+0.65
(Calculation example) 3.74 s when the module is mounted on the main base unit, the number of
settings is 1, and the number of X points is 16
<Main base unit>
• 16 words or less
Time = 0.47
(total number of transferred words)+2.85
• More than 16 words
Time = 0.5
(total number of transferred words)+0.95
<Extension base unit>
• 16 words or less
Time = 1.07
(total number of transferred words)+2.85
• More than 16 words
Time = 1.1
(total number of transferred words)+0.95
(Calculation example) 4.74 s when the module is mounted on the main base unit, thenumber of
settings is 1, and the number of words is 2
41 s
Depends on the user-created interrupt program.
<Main base unit>
• 16 words or less
Time = 0.47
(total number of transferred words)+2.65
• More than 16 words
Time = 0.55
(total number of transferred words)+0.95
<Extension base unit>
• 16 words or less
Time = 1.07
(total number of transferred words)+2.65
• More than 16 words
Time = 1.15
(total number of transferred words)+0.95
(Calculation example) 4.54 s when the module is mounted on the main base unit, the number of
settings is 1, and the number of words is 2
<Main base unit>
Time = 0.13
(total number of Y points) +1.55
<Extension base unit>
Time = 0.2
(total number of Y points)+1.55
(Calculation example) 3.63 s when the module is mounted on the main base unit, the number of
settings is 1, and the number of Y points is 16
Processing Time
(number of settings)+0.85
(number of settings)+0.85
(number of settings)+0.95
(number of settings)+0.95
(number of settings)+0.95
(number of settings) + 0.95
6.22 High Speed Interrupt Function
6.22.3 Processing times
1
2
3
4
5
6
7
8
6
- 144

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents