Section 2: Configuration
June 2012
2.10.2
Sensor Temperature Unit
The Sensor Temperature Unit command selects between Celsius and Fahrenheit units for the
sensor temperature. The sensor temperature output is accessible via HART only.
To select the sensor temperature unit:
1.
2.
3.
4.
5.
2.11
Diagnostics and Service
Diagnostics and service functions listed below are primarily for use after field installation. The
Transmitter Test feature is designed to verify that the transmitter is operating properly, and can
be performed either on the bench or in the field.
2.11.1
Master Reset
The master reset function will reset the device electronics. To perform a master reset:
1.
2.
3.
4.
2.11.2
Join Status
To view the join status of the device, perform the following procedure:
1.
2.
3.
20
Fast Keys
2, 2, 3, 1, 1
From the Home screen, select 2: Configure.
Select 2: Manual Setup.
Select 3: Device Temperatures.
Select 1: Sensor Temperature.
Select 1: Unit to select from Celsius or Fahrenheit.
Fast Keys
3, 4, 2, 1
From the Home screen, select 3: Service Tools.
Select 4: Routine Maintenance.
Select 2: Other.
Select 1: Master Reset.
Fast Keys
3, 3, 1
From the Home screen, select 3: Service Tools.
Select 3: Communications.
Select 1: Join Status.