Quick Start Guide
00825-0100-4797, Rev HA
January 2020
Rosemount
3051 Pressure Transmitter
and Rosemount 3051CF Series Flow
Meter
®
with PROFIBUS
PA Protocol

Advertisement

loading
Need help?

Need help?

Do you have a question about the Rosemount 3051CF Series and is the answer not in the manual?

Questions and answers

Summary of Contents for Emerson Rosemount 3051CF Series

  • Page 1 Quick Start Guide 00825-0100-4797, Rev HA January 2020 ™ Rosemount 3051 Pressure Transmitter and Rosemount 3051CF Series Flow Meter ® with PROFIBUS PA Protocol...
  • Page 2: Table Of Contents

    Quick Start Guide January 2020 Contents About this guide...........................3 Transmitter installation........................ 5 Basic configuration........................26 Trim the transmitter........................29 Product certifications......................... 30 Emerson.com/Rosemount...
  • Page 3: About This Guide

    (I.S.) installations. Refer to the Rosemount 3051 Reference Manual Rosemount 3051 Reference Manual for more instructions. This manual is also available electronically on Emerson.com/Rosemount. WARNING Explosions Explosions could result in death or serious injury. Installation of this transmitter in an explosive environment must be in accordance with the local, national, and international standards, codes, and practices.
  • Page 4 Physical security is an important part of any security program and fundamental to protecting your system. Restrict physical access by unauthorized personnel to protect end users’ assets. This is true for all systems used within the facility. Emerson.com/Rosemount...
  • Page 5: Transmitter Installation

    January 2020 Quick Start Guide Transmitter installation Mount the transmitter For dimensional drawing information refer to the Dimensional Drawings section of the Rosemount 3051 Product Data Sheet. Figure 2-1: Panel Mount Coplanar Flange 5/16 x 1½ panel bolts are customer supplied. Quick Start Guide...
  • Page 6 Quick Start Guide January 2020 Figure 2-2: Pipe Mount Coplanar Flange Figure 2-3: Panel Mount Traditional Flange Figure 2-4: Pipe Mount Traditional Flange Emerson.com/Rosemount...
  • Page 7 January 2020 Quick Start Guide Figure 2-5: Panel Mount Rosemount 3051T Figure 2-6: Pipe Mount Rosemount 3051T Quick Start Guide...
  • Page 8 Figure 2-7: Mounting the Transmitter in Liquid Applications In-line 2.1.2 Mount the transmitter in gas applications Procedure 1. Place taps in the top or side of the line. 2. Mount beside or above the taps. Figure 2-8: Mounting the Transmitter in Gas Applications In-line Emerson.com/Rosemount...
  • Page 9 If the transmitter installation requires assembly of the process flanges, manifolds, or flange adapters, follow the assembly guidelines to ensure a tight seal for optimal performance characteristics of the transmitters. Use only bolts supplied with the transmitter or sold by Emerson as spare parts. Figure 2-10 illustrates common transmitter assemblies with the bolt length required for proper transmitter assembly.
  • Page 10 2-1. If bolt material is not shown in Table 2-1, contact a local Emerson representative for more information. Carbon steel bolts do not require lubrication, and the stainless steel bolts are coated with a lubricant to ease installation. However, do not apply additional lubricant when installing either type of bolt.
  • Page 11 January 2020 Quick Start Guide Procedure 1. Use the fingers to tighten the bolts. 2. Torque the bolts to the initial torque value using a crossing pattern. Table 2-1 for initial torque value. 3. Torque the bolts to the final torque value using the same crossing pattern.
  • Page 12 Keep the vent path free of any obstruction, such as paint, dust, and lubrication, by mounting the transmitter so that the process can drain away. Figure 2-12: Inline Gage Low Side Pressure Port A. Low side pressure port (atmospheric reference) Emerson.com/Rosemount...
  • Page 13 January 2020 Quick Start Guide CAUTION Electronics damage Rotation between the sensor module and the process connection can damage the electronics. Do not apply torque directly to the sensor module. To avoid damage, apply torque only to the hex-shaped process connection.
  • Page 14 PHYSICAL DEVICE TAG A. Device revision Note The device description loaded in the host system must be at the same revision as this device. You can download the device description from the host system website or Emerson.com/Rosemount by selecting Device Emerson.com/Rosemount...
  • Page 15 January 2020 Quick Start Guide Drivers under Resources. You can also visit and select End User Fieldbus.org Resources. Consider housing rotation To improve field access to wiring or to better view the optional LCD display: Figure 2-14: Housing Rotation A. Housing rotation set screw (5/64-in.) Procedure 1.
  • Page 16 3. Slide the Security and Simulate switches into the preferred position. 4. Replace the housing cover. Note Emerson recommends tightening the cover until there is no gap between the cover and the housing. Emerson.com/Rosemount...
  • Page 17 9 Vdc. Power supply voltage can be variable, especially under abnormal conditions, such as when operating on battery backup. Emerson recommends a minimum of 12 Vdc under normal operating conditions and shielded twisted pair Type A cable.
  • Page 18 Note Emerson does not recommend using a pin or ferrule wire terminal, as the connection may be more susceptible to loosening over time or under vibration.
  • Page 19 Note Improper grounding is the most frequent cause of poor segment communications. 3. Replace the housing cover. Emerson recommends tightening the cover until there is no gap between the cover and the housing. 4. Plug and seal unused conduit connections.
  • Page 20 When you exit the Locate Device method, the device LCD display automatically returns to normal operation. Note Some hosts do not support Locate Device in the DD. Connect the power module Procedure 1. Remove the power module cover. 2. Connect the green power module (see Figure 2-18). Emerson.com/Rosemount...
  • Page 21 January 2020 Quick Start Guide Figure 2-18: Power Module A. Power module Trim the transmitter Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on gage and differential pressure transmitters to eliminate error due to mounting position or static pressure effects. A zero trim can be performed using either a Field Communicator or configuration buttons.
  • Page 22 • At the device via the Local Display (LCD display). • By using the Field Communicator. • Via the Emerson Wireless Gateway’s integrated web interface. • Via AMS Wireless Configurator. 2.9.1 Verify transmitter configuration using LCD display The LCD display will show the output values at the same rate as the wireless update rate.
  • Page 23 January 2020 Quick Start Guide error codes and other LCD display messages. Press and hold the Diagnostic button for at least five seconds to display the TAG, Device ID, Network ID, Network Join Status, and Device Status screens. Searching for Joining network Connected with Connected...
  • Page 24 Simulate Digital Signal 3, 6 2.9.3 Verify transmitter configuration using Emerson Wireless Gateway In the Gateway’s integrated web interface, navigate to the Explorer > Status page. This page will show whether the device has joined the network and if it is communicating properly.
  • Page 25 January 2020 Quick Start Guide 2.9.4 Verifying configuration using AMS Wireless Configurator When the device has joined the network, it will appear in the AMS Wireless Configurator as shown in Figure 2-21. Figure 2-21: Wireless Configurator Network Setup Quick Start Guide...
  • Page 26: Basic Configuration

    Unless otherwise requested, the Rosemount 3051 Pressure Transmitter ships with the following settings: • Measurement mode: Pressure • Engineering units: inches H • Scaling: None Engineering units should be confirmed or configured before installation. Units can be configured for Pressure, Flow or Level measurement. Emerson.com/Rosemount...
  • Page 27 Characters blink when they can be changed. Figure 3-1: LOI Menu Class 2 Master The Rosemount 3051 Profibus DD and DTM files are available at Emerson.com/Rosemount or by contacting your local salesperson. See Table for steps to configure the transmitter for Pressure measurement. See the...
  • Page 28 3051 specific (rmt4444.gsd) or Profile 3.02 Generic (pa139700.gsd). These files can be found on Emerson.com/Rosemount or Profibus.com. Configuration host (Class 2) The appropriate DD or DTM file must be installed in the configuration host. These files can be found at Emerson.com/Rosemount. Emerson.com/Rosemount...
  • Page 29: Trim The Transmitter

    January 2020 Quick Start Guide Trim the transmitter Devices are calibrated by the factory. Once installed, it is recommended to perform a zero trim on the sensor to eliminate error due to mounting position or static pressure effects. This can be done by performing a zero trim via: •...
  • Page 30: Product Certifications

    A copy of the EU Declaration of Conformity can be found at the end of the Quick Start Guide. The most recent revision of the EU Declaration of Conformity can be found at Emerson.com/Rosemount. Ordinary location certification As standard, the transmitter has been examined and tested to determine...
  • Page 31 January 2020 Quick Start Guide Standards FM Class 3600 - 2011, FM Class 3610 - 2010, FM Class 3611 - 2004, FM Class 3810 - 2005, ANSI/NEMA 250 - 2008 Markings IS CL I, DIV 1, GP A, B, C, D; CL II, DIV 1, GP E, F, G; Class III; DIV 1 when connected per Rosemount drawing 03031-1019;...
  • Page 32 Standards ANSI/ISA 12.27.01-2003, CSA Std. C22.2 No. 30 -M1986, CSA Std. C22.2 No.142-M1987, CSA Std. C22.2 No. 213 - M1987 Markings Explosionproof Class I, Division 1, Groups B, C, and D; Suitable for Class I, Zone 1, Group IIB+H2, T5; Emerson.com/Rosemount...
  • Page 33 January 2020 Quick Start Guide Dust-Ignitionproof for Class II and Class III, Division 1, Groups E, F, and G; T5 (–50 °C ≤ Ta ≤ +85 °C); Class I, Division 2, Groups A, B, C, and D; T5; Suitable for Class I Zone 2, Group IIC;...
  • Page 34 3. Some variants of the equipment have reduced markings on the nameplate. Refer to the Certificate for full equipment marking. 5.4.3 IA ATEX FISCO Certificate BAS97ATEX1089X Standards EN60079-0:2012 + A11:2013, EN60079-11:2012 Markings II 1 G Ex ia IIC T4 Ga (–60 °C ≤ T ≤ +60 °C) Emerson.com/Rosemount...
  • Page 35 January 2020 Quick Start Guide Table 5-3: Input Parameters Parameter Fieldbus/PROFIBUS Voltage U 17.5 V Current I 380 mA Power P 5.32 W Capacitance C ≤5 nF Inductance L ≤10 µH Special Conditions for Safe Use (X): 1. The apparatus is not capable of withstanding the 500 V insulation test required by clause 6.3.12 of EN60079-11: 2012.
  • Page 36 HART: Ex ia IIC T5/T4 Ga, T5(-60 °C ≤ T ≤ +40 °C), T4 (-60 °C ≤ ≤ +70 °C) Fieldbus/PROFIBUS: Ex ia IIC T4(–60 °C ≤ T ≤ +60 °C) Table 5-5: Input Parameters Parameter HART Fieldbus/PROFIBUS Voltage U 30 V 30 V Emerson.com/Rosemount...
  • Page 37 January 2020 Quick Start Guide Table 5-5: Input Parameters (continued) Parameter HART Fieldbus/PROFIBUS Current I 200 mA 300 mA Power P 0.9 W 1.3 W Capacitance C 0.012 µF 0 µF Inductance L 0 mH 0 mH Special Conditions for Safe Use (X): 1.
  • Page 38 ≤ +70 °C) Special Condition for Safe Use (X): 1. This apparatus is not capable of withstanding the 500 V insulation test required by clause 6.5.1 of IEC 60079-15. This must be taken into account when installing the apparatus. Emerson.com/Rosemount...
  • Page 39 January 2020 Quick Start Guide Brazil 5.6.1 E2 INMETRO Flameproof Certificate UL-BR 13.0643X Standards ABNT NBR IEC 60079-0:2013; ABNT NBR IEC 60079-1:2016; ABNT NBR IEC 60079-26:2016 Markings Ex db IIC T6…T4 Ga/Gb, T6(–60 °C ≤ Ta ≤ +70 °C), T4/T5 (–60 °C ≤...
  • Page 40 ABNT NBR IEC 60079-11. This must be taken into account when installing the equipment. 2. The enclosure may be made of aluminum alloy and given protective polyurethane paint finish; however, care should be taken to protect it from impact or abrasion if equipment requires EPL Ga. Emerson.com/Rosemount...
  • Page 41 January 2020 Quick Start Guide China 5.7.1 E3 China Flameproof Certificate GYJ19.1056X [Transmitters]; GYJ15.1368X [Flow meters] Standards GB3836.1-2010, GB3836.2-2010, GB3836.20-2010, GB12476.1-2013, GB12476.5-2013 Markings 3051 Series: Ex d IIC T6 ~ T4 Ga/Gb, Ex tD A20 IP66 T95 °C T 105 °C (-20 °C ≤ Ta ≤ +85 °C) 3051CF Series: Ex d IIC T5/T6 Ga/Gb 一、产品安全使用特殊条件...
  • Page 42 产品安全使用特殊条件: • 证书编号后缀“X”表明产品具有安全使用特殊条件: 1. 产品(选用铝合金外壳)外壳含有轻金属,用于 0 区时需注意 防止由于冲击或摩擦产生的点燃危险。 2. 当选择 T1 瞬态抑制端子时,此设备不能承受 GB3836.4-2010 标 准中第 6.3.12 条规定的 500V 交流有效值试验电压的介电强度 试验。 3. Transmitter output 为 X 时,需使用由厂家提供的型号为 701PG 的 Smart Power Green Power Module 电池。 4. 产品外壳含有非金属部件,使用时须防止产生静电火花,只能 用湿布清理。 产品使用注意事项: • Emerson.com/Rosemount...
  • Page 43 January 2020 Quick Start Guide 1. 产品使用环境温度范围: 气体/粉尘 温度组别 环境温度范围 Transmitter output 气体 A, M -60 °C ~ +40 °C 气体 A, M -60 °C ~ +70 °C 气体 F, W -60 °C ~ +60 °C 气体 -40 °C ~ +70 °C 粉尘...
  • Page 44 1. 产品使用环境温度范围为: -40 °C ≤ T ≤ 70 °C 2. 最高输入电压: 最高输入电压 Transmitter output A, M (3051 Enhanced & 3051 Low 55 Vdc Power HART F, W 40 Vdc 3. 现场安装时,电缆引入口须选用经国家指定的防爆检验机构检 验认可的、具有 Ex e 或 Ex n 型的电缆引入装置或堵封件,冗余 电缆引入口须用堵封件有效密封。 Emerson.com/Rosemount...
  • Page 45 January 2020 Quick Start Guide 4. 安装现场确认无可燃性气体存在时方可维修。 5. 用户不得自行更换该产品的零部件,应会同产品制造商共同解 决运行中出现的故障,以杜绝损坏现象的发生。 6. 产品的安装、使用和维护应同时遵守产品使用说明书、 GB3836.13-2013“爆炸性环境 第 13 部分:设备的修理、检修、 修复和改造”、GB3836.15-2000“爆炸性气体环境用电气设备 第 15 部分:危险场所电气安装(煤矿除外)”、GB3836.16-2006 “爆炸性气体环境用电气设备 第 16 部分:电气装置的检查和维 护(煤矿除外)” 、GB50257-1996“电气装置安装工程爆炸和火 灾危险环境电力装置施工及验收规范”的有关规定。 Japan 5.8.1 E4 Japan Flameproof Certificate TC20577, TC20578, TC20583, TC20584 [HART]; TC20579, TC20580, TC20581, TC20582 [Fieldbus] Markings Ex d IIC T5 Republic of Korea...
  • Page 46 Ex de IIC Gb 5.12.2 ATEX Flameproof and Increased Safety Certificate FM13ATEX0076X Standards EN60079-0:2012, EN60079-1:2007, IEC60079-7:2007 Markings II 2 G Ex de IIC Gb Table 5-10: Conduit Plug Thread Sizes Thread Identification mark M20 × 1.5 ½ –14 NPT ½ NPT Emerson.com/Rosemount...
  • Page 47 January 2020 Quick Start Guide Table 5-11: Thread Adapter Thread Sizes Male thread Identification mark M20 × 1.5 – 6H ½–14 NPT ½ –14 NPT ¾ –14 NPT ¾ –14 NPT Female thread Identification mark M20 × 1.5 – 6H ½–14 NPT ½–14 NPT G½...
  • Page 48 Application Table 5-12: Location Classes Temperature Humidity Vibration Enclosure 5.13.4 SLL Lloyds Register (LR) Type Approval Certificate 11/60002 Application Environmental categories ENV1, ENV2, ENV3, and ENV5 5.13.5 C5 Custody Transfer - Measurement Canada Accuracy Approval Certificate AG-0226; AG-0454; AG-0477 Emerson.com/Rosemount...
  • Page 49 January 2020 Quick Start Guide 5.14 EU Declaration of Conformity Quick Start Guide...
  • Page 50 Quick Start Guide January 2020 Emerson.com/Rosemount...
  • Page 51 January 2020 Quick Start Guide Quick Start Guide...
  • Page 52 Quick Start Guide January 2020 Emerson.com/Rosemount...
  • Page 53 January 2020 Quick Start Guide 5.15 China RoHS table Rosemount 3051 China RoHS List of Rosemount 3051 Parts with China RoHS Concentration above MCVs / Hazardous Substances Hexavalent Polybrominated Polybrominated Part Name Lead Mercury Cadmium Chromium biphenyls diphenyl ethers (Pb) (Hg) (Cd) (Cr +6)