Emerson Rosemount 2051 Wireless Series Reference Manual page 64

Pressure, level, and flow solutions with wirelesshart protocol
Hide thumbs Also See for Rosemount 2051 Wireless Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4102, Rev AA
Rosemount 2051CD/CG
Range 0: 750 psi (51,7 bar)
Range 1: 2000 psig (137,9 bar)
Ranges 2–5: 3626 psig (250 bar)
Rosemount 2051CA
Range 1: 750 psia (51,7 bar)
Range 2: 1500 psia (103,4 bar)
Range 3: 1600 psia (110,3 bar)
Range 4: 6000 psia (413,7 bar)
Rosemount 2051H
All Ranges: 3626 psig (25 MPa)
Rosemount 2051TG/TA
Range 1: 750 psi (51,7 bar)
Range 2: 1500 psi (103,4 bar)
Range 3: 1600 psi (110,3 bar)
Range 4: 6000 psi (413,7 bar)
Range 5: 15000 psi (1034,2 bar)
Rosemount 2051L
Limit is flange rating or sensor rating, whichever is lower (see the table below).
Standard
ANSI/ASME
ANSI/ASME
ANSI/ASME
DIN
DIN
DIN
At 248 °F (120 °C), the rating decreases with increasing temperature, per DIN 2401.
Static Pressure Limit
Rosemount 2051CD Only
Operates within specifications between static line pressures of 0.5 psia and 3626 psig (4500 psig
(310, 3 bar) for
Option Code P9).
Range 0: 0.5 psia and 750 psig (3, 4 bar and 51, 7 bar)
Range 1: 0.5 psia and 2000 psig (3, 4 bar and 137, 9 bar)
Specifications and Reference Data
4500 psig (310,3 bar) for option code P9
Type
Class 150
Class 300
Class 600
At 100 °F (38 °C), the rating decreases
with increasing temperature, per ANSI/ASME B16.5.
PN 10–40
PN 10/16
PN 25/40
CS Rating
SST Rating
285 psig
275 psig
740 psig
720 psig
1480 psig
1440 psig
40 bar
40 bar
16 bar
16 bar
40 bar
40 bar
Appendix A: Reference Data
June 2012
77