Section 6: Troubleshooting
June 2012
Device Status
Description
HI Alarm
The primary variable has surpassed
the user defined limit.
LO Alarm
The primary variable has surpassed
the user defined limit.
LO LO Alarm
The primary variable has surpassed
the user defined limit.
Button Stuck
A buttons on the Electronics Board
is detected as stuck in the active
position.
Simulation Active
The device is in simulation mode
and may not be reporting actual
information.
70
Recommended Action
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Check the buttons for obstructions
2.
Reset the device
3.
If the condition persists, replace the electronics
1.
Verify that simulation is no longer required
2.
Disable Simulation mode in Service Tools
3.
Reset the device
Reference Manual
00809-0100-4100, Rev AA
Troubleshooting