Reference Manual
00809-0100-4102, Rev AA
Field Hook-up
Figure 2-1
Communicator or AMS may be connected at "COMM" on the transmitter terminal block.
Figure 2-1. Field Communicator Connection
For HART communication, a 2051 WirelessHART DD is required.
2.4
Device Network Configuration
2.4.1
Join Device to Network
In order to communicate with the Smart Wireless Gateway, and ultimately the Host System, the
transmitter must be configured to communicate over the wireless network. This step is the
wireless equivalent of connecting wires from a transmitter to the host system.
1.
2.
3.
Using a Field Communicator or AMS, enter the Network ID and Join Key so that they match the
Network ID and Join Key of the Smart Wireless Gateway and other devices in the network. If the
Network ID and Join Key are not identical to those set in the Gateway, the transmitter will not
communicate with the network. The Network ID and Join Key may be obtained from the Smart
Wireless Gateway on the Setup>Network>Settings page on the web server.
Configuration
illustrates the wiring for a field hook-up with a Field Communicator or AMS. The Field
Fast Keys
2, 1, 1
From the Home screen, select 2: Configure.
Select 1: Guided Setup.
Select 1: Join Device to Network.
Section 2: Configuration
June 2012
7