Section 5: Operation and Maintenance
June 2012
Note
Use the Rosemount Wireless LCD Part Number: 00753-9004-0002.
66
c o n f g
w a r n
s n s r
f a i l u r
s n s r
w a r n
Diagnostic Button Screen 9.2:
configuration of the transmitter is
invalid such that non-critical
operation of the device may be
affected - check the extended
configuration status to identify
which configuration item(s) need
to be corrected
Diagnostic Button Screen 10.1: a
sensor attached to the
transmitter has failed, and valid
readings from that sensor are no
longer possible - check the sensor
and sensor wiring connections -
check additional status for more
detailed information of the failure
source
Diagnostic Button Screen 10.2: a
sensor attached to the
transmitter is degraded, readings
from that sensor may not be
within accuracy specifications -
check the process, and sensor
wiring connections - check
additional status for more
detailed information of the
warning source
Operation and Maintenance
Reference Manual
00809-0100-4100, Rev AA