Emerson Rosemount 2051 Wireless Series Reference Manual page 52

Pressure, level, and flow solutions with wirelesshart protocol
Hide thumbs Also See for Rosemount 2051 Wireless Series:
Table of Contents

Advertisement

Reference Manual
00809-0100-4102, Rev AA
Device Status
Description
Configuration Error
The device has detected a
configuration error based on a
change to the device.
HI HI Alarm
The primary variable has surpassed
the user defined limit.
HI Alarm
The primary variable has surpassed
the user defined limit.
LO Alarm
The primary variable has surpassed
the user defined limit.
LO LO Alarm
The primary variable has surpassed
the user defined limit.
Button Stuck
A buttons on the Electronics Board
is detected as stuck in the active
position.
Simulation Active
The device is in simulation mode
and may not be reporting actual
information.
Troubleshooting
Recommended Action
1.
Click on details for more information
2.
Correct the parameter that has a configuration error
3.
Reset the device
4.
If the condition persists, replace the electronics
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Verify that the process variable is within user
specified limits
2.
Reconfirm the user defined alarm limit
3.
If not needed, disable this alert
1.
Check the buttons for obstructions
2.
Reset the device
3.
If the condition persists, replace the electronics
1.
Verify that simulation is no longer required
2.
Disable Simulation mode in Service Tools
3.
Reset the device
Section 6: Troubleshooting
June 2012
65