5.7 CONTROL ELEMENTS
1
2
3
4
5
6
7
8
9
10
Figure 5–118: EXAMPLE FLEXLOGIC™ CONTROL OF A SETTINGS GROUP
PATH: SETTINGS
CONTROL ELEMENTS

SELECTOR SWITCH 1

5
5-210
VIRT IP 1 ON (VI1)
OR (2)
CONT IP 1 ON (H5A)
OR (2)
PHASE TOC1 PKP
NOT
PHASE TOC2 PKP
NOT
AND (3)
= VIRT OP 1 (VO1)
END
SELECTOR SWITCH
SELECTOR 1 FUNCTION:
Disabled
SELECTOR 1 FULL
MESSAGE
RANGE: 7
SELECTOR 1 TIME-OUT:
MESSAGE
5.0 s
SELECTOR 1 STEP-UP:
MESSAGE
Off
SELECTOR 1 STEP-UP
MESSAGE
MODE: Time-out
SELECTOR 1 ACK:
MESSAGE
Off
SELECTOR 1 3BIT A0:
MESSAGE
Off
SELECTOR 1 3BIT A1:
MESSAGE
Off
SELECTOR 1 3BIT A2:
MESSAGE
Off
SELECTOR 1 3BIT
MESSAGE
MODE: Time-out
SELECTOR 1 3BIT ACK:
MESSAGE
Off
SELECTOR 1 POWER-UP
MESSAGE
MODE: Restore
SELECTOR 1 TARGETS:
MESSAGE
Self-reset
SELECTOR 1 EVENTS:
MESSAGE
Disabled
L90 Line Current Differential System
AND (3)
= VIRT OP 1 (VO1)
SELECTOR SWITCH 1(2)
Range: Disabled, Enabled
Range: 1 to 7 in steps of 1
Range: 3.0 to 60.0 s in steps of 0.1
Range: FlexLogic™ operand
Range: Time-out, Acknowledge
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: FlexLogic™ operand
Range: Time-out, Acknowledge
Range: FlexLogic™ operand
Range: Restore, Synchronize, Sync/Restore
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
5 SETTINGS
842789A1.CDR
5.7.4 SELECTOR SWITCH