5.6 CONTROL ELEMENTS

PATH: SETTINGS
CONTROL ELEMENTS
 SELECTOR SWITCH 1
5
The selector switch element is intended to replace a mechanical selector switch. Typical applications include setting group
control or control of multiple logic sub-circuits in user-programmable logic.
The element provides for two control inputs. The step-up control allows stepping through selector position one step at a
time with each pulse of the control input, such as a user-programmable pushbutton. The three-bit control input allows set-
ting the selector to the position defined by a three-bit word.
The element allows pre-selecting a new position without applying it. The pre-selected position gets applied either after time-
out or upon acknowledgement via separate inputs (user setting). The selector position is stored in non-volatile memory.
Upon power-up, either the previous position is restored or the relay synchronizes to the current three-bit word (user set-
ting). Basic alarm functionality alerts the user under abnormal conditions; for example, the three-bit control input being out
of range.
A selector switch runs every two power cycles.
SELECTOR 1 FULL RANGE: This setting defines the upper position of the selector. When stepping up through avail-
able positions of the selector, the upper position wraps up to the lower position (position 1). When using a direct three-
bit control word for programming the selector to a desired position, the change would take place only if the control word
is within the range of 1 to the
by setting the
SELECTOR ALARM
5-228


SELECTOR SWITCH

SELECTOR 1 FUNCTION:
Disabled
SELECTOR 1 FULL
MESSAGE
RANGE: 7
SELECTOR 1 TIME-OUT:
MESSAGE
5.0 s
SELECTOR 1 STEP-UP:
MESSAGE
Off
SELECTOR 1 STEP-UP
MESSAGE
MODE: Time-out
SELECTOR 1 ACK:
MESSAGE
Off
SELECTOR 1 3BIT A0:
MESSAGE
Off
SELECTOR 1 3BIT A1:
MESSAGE
Off
SELECTOR 1 3BIT A2:
MESSAGE
Off
SELECTOR 1 3BIT
MESSAGE
MODE: Time-out
SELECTOR 1 3BIT ACK:
MESSAGE
Off
SELECTOR 1 POWER-UP
MESSAGE
MODE: Restore
SELECTOR 1 TARGETS:
MESSAGE
Self-reset
SELECTOR 1 EVENTS:
MESSAGE
Disabled
SELECTOR FULL RANGE
FlexLogic operand for 3 seconds.
L60 Line Phase Comparison System
SELECTOR SWITCH 1(2)
Range: Disabled, Enabled
Range: 1 to 7 in steps of 1
Range: 3.0 to 60.0 s in steps of 0.1
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: FlexLogic operand
Range: Time-out, Acknowledge
Range: FlexLogic operand
Range: Restore, Synchronize, Sync/Restore
Range: Self-reset, Latched, Disabled
Range: Disabled, Enabled
. If the control word is outside the range, an alarm is established
5 SETTINGS
5.6.4 SELECTOR SWITCH