5.2 PRODUCT SETUP
PATH: SETTINGS
PRODUCT SETUP
 USER-PROGRAMMABLE
 SELF TESTS
5
All major self-test alarms are reported automatically with their corresponding FlexLogic operands, events, and targets. Most
of the minor alarms can be disabled if desired.
When in the Disabled mode, minor alarms do not assert a FlexLogic operand, write to the event recorder, or display target
messages. Moreover, they do not trigger the
minor alarms continue to function along with other major and minor alarms. See the Relay Self-tests section in chapter 7 for
information on major and minor self-test alarms.
PATH: SETTINGS
PRODUCT SETUP
 CONTROL
 PUSHBUTTON 1
There are three standard control pushbuttons, labeled USER 1, USER 2, and USER 3, on the standard and enhanced front
panels. These are user-programmable and can be used for various applications such as performing an LED test, switching
setting groups, and invoking and scrolling though user-programmable displays.
5-78

USER-PROGRAMMABLE SELF TESTS
REMOTE DEVICE OFF
FUNCTION: Enabled
FIRST ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
SEC. ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
THIRD ETHERNET FAIL
MESSAGE
FUNCTION: Disabled
BATTERY FAIL
MESSAGE
FUNCTION: Enabled
SNTP FAIL
MESSAGE
FUNCTION: Enabled
IRIG-B FAIL
MESSAGE
FUNCTION: Enabled
PTP FAIL
MESSAGE
FUNCTION: Enabled
SFP MODULE FAIL
MESSAGE
FUNCTION: Disabled
ANY MINOR ALARM


CONTROL PUSHBUTTONS

CONTROL PUSHBUTTON 1
FUNCTION: Disabled
CONTROL PUSHBUTTON 1
MESSAGE
EVENTS: Disabled
L30 Line Current Differential System

5.2.11 USER-PROGRAMMABLE SELF-TESTS

Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
Range: Disabled, Enabled.
or
messages. When in Enabled mode,
ANY SELF-TEST
5.2.12 CONTROL PUSHBUTTONS
CONTROL PUSHBUTTON 1(7)
Range: Disabled, Enabled
Range: Disabled, Enabled
5 SETTINGS