Chapter 23 - Technical Specifications
14.6

SURGE IMMUNITY TEST

Compliance
Pulse duration
Between all groups and protective earth conductor terminal
Between terminals of each group (excluding communications ports,
where applicable)
14.7

IMMUNITY TO RADIATED ELECTROMAGNETIC ENERGY

Compliance
Frequency band
Spot tests at
Test field strength
Test using AM
Compliance
Frequency band
Spot tests at
Waveform
Field strength
14.8

RADIATED IMMUNITY FROM DIGITAL COMMUNICATIONS

Compliance
Frequency bands
Test field strength
Test using AM
14.9

RADIATED IMMUNITY FROM DIGITAL RADIO TELEPHONES

Compliance
Frequency bands
Test field strength
14.10
IMMUNITY TO CONDUCTED DISTURBANCES INDUCED BY RADIO FREQUENCY
FIELDS
Compliance
Frequency bands
558
IEC 61000-4-5: 2005 Level 4, IEC 60255-26:2013
Time to half-value: 1.2/50 µs
Amplitude 4 kV
Amplitude 2 kV
IEC 60255-22-3: 2007, Class III, IEC 60255-26:2013
80 MHz to 3.0 GHz
80, 160, 380, 450, 900, 1850, 2150 MHz
10 V/m
1 kHz @ 80%
IEEE/ANSI C37.90.2: 2004
80 MHz to 1 GHz
80, 160, 380, 450 MHz
1 kHz @ 80% am and pulse modulated
35 V/m
IEC 61000-4-3: 2006, Level 4, IEC 60255-26:2013
800 to 960 MHz, 1.4 to 2.0 GHz
30 V/m
1 kHz / 80%
IEC 61000-4-3: 2006, IEC 60255-26:2013
900 MHz and 1.89 GHz
10 V/m
IEC 61000-4-6: 2008, Level 3, IEC 60255-26:2013
150 kHz to 80 MHz
P14x