P14x
7.4.1

PHYSICAL CONNECTION AND LINK LAYER

Two connection options are available for MODBUS
Rear Port 1 (RP1) - for permanent SCADA connection via RS485
Optional fibre port (RP1 in slot A) - for permanent SCADA connection via optical fibre
The MODBUS interface uses 'RTU' mode communication rather than 'ASCII' mode as this provides more efficient
use of the communication bandwidth. This mode of communication is defined by the MODBUS standard.
The IED address and baud rate can be selected using the front panel menu or by the settings application software.
When using a serial interface, the data format is: 1 start bit, 8 data bits, 1 parity bit with 1 stop bit, or 2 stop bits (a
total of 11 bits per character).
7.4.2

MODBUS FUNCTIONS

The following MODBUS function codes are supported:
01: Read Coil Status
02: Read Input Status
03: Read Holding Registers
04: Read Input Registers
06: Preset Single Register
08: Diagnostics
11: Fetch Communication Event Counter
12: Fetch Communication Event Log
16: Preset Multiple Registers 127 max
These are interpreted by the MiCOM IED in the following way:
01: Read status of output contacts (0xxxx addresses)
02: Read status of opto inputs (1xxxx addresses)
03: Read setting values (4xxxx addresses)
04: Read measured values (3xxxx addresses
06: Write single setting value (4xxxx addresses)
16: Write multiple setting values (4xxxx addresses)
7.4.3

RESPONSE CODES

MCode
MODBUS Description
01
Illegal Function Code
02
Illegal Data Address
03
Illegal Value
06
Slave Device Busy
P14xEd1-TM-EN-1
The function code transmitted is not supported by the slave.
The start data address in the request is not an allowable value. If any of the addresses in
the range cannot be accessed due to password protection then all changes within the
request are discarded and this error response will be returned.
Note: If the start address is correct but the range includes non–implemented addresses
this response is not produced.
A value referenced in the data field transmitted by the master is not within range. Other
values transmitted within the same packet will be executed if inside range.
The write command cannot be implemented due to the database being locked by another
interface. This response is also produced if the software is busy executing a previous
request.
Chapter 18 - Communications
MiCOM Interpretation
431