Figure 116: Star connected condenser bushings

Calculations for Condenser Bushing Systems
Consider a single-phase fault to ground on B-Phase:
V
c
E00820

Figure 117: Theoretical earth fault in condenser bushing system

222
E00819
V
a
N
V
b
I
C
Neutral Voltage
Displacement Relay
(NVD)
I
A
I
F
-jXc
-jXc
-jXc
P14xEd1-TM-EN-1