GE MiCOM P40 Agile Technical Manual page 632

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

CUSTOMER SETTING
NOTE:
3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO ENSURE
CORRECT OPERATION OF THE PROTECTIVE RELAY.
Issue:
Revision:
DRAWING OUTLINE UPDATED . CID BLIN-8BHLDT
D
Date:
25/11/2010
Name:
W.LINTERN
CAD DATA 1:1 DIMENSIONS: mm
DO NOT SCALE
Date:
Chkd:
DEFAULT SETTING
D1
-
OPTO 1
L1 Setting Group
D2
+
D3
-
OPTO 2
L2 Setting Group
D4
+
D5
-
OPTO 3
L3 Block IN1>3&4
D6
+
D7
-
OPTO 4
L4 Block I>3&4
D8
+
D9
-
OPTO 5
L5 Reset LEDs
D10
+
D11
-
OPTO 6
L6 External Trip
D12
+
D13
-
OPTO 7
L7 52-A
D14
+
D15
-
OPTO 8
L8 52-B
D16
+
D17
COMMON
D18
CONNECTION
F1
-
OPTO 9
L9 Select Auto
F2
+
F3
-
OPTO 10
L10 Sel Telecntl
F4
+
F5
-
OPTO 11
L11 Sel LiveLine
F6
+
F7
-
L12 CB Healthy
OPTO 12
F8
+
F9
-
OPTO 13
L13 Block AR
F10
+
F11
-
OPTO 14
L14 Reset Lckout
F12
+
F13
-
OPTO 15
L15 Not Used
F14
+
F15
-
OPTO 16
L16 Not Used
F16
+
F17
COMMON
F18
CONNECTION
MiCOM P143
(PART)
ALSTOM GRID UK LTD
Substation Automation Solutions
J11
WATCHDOG
J12
CONTACT
J13
WATCHDOG
J14
CONTACT
H1
RELAY 1
H2
H3
RELAY 2
H4
H5
SEE NOTE 3
RELAY 3
H6
H7
H8
RELAY 4
H9
H10
H11
RELAY 5
H12
H13
H14
RELAY 6
H15
H16
H17
RELAY 7
H18
G1
RELAY 8
G2
G3
RELAY 9
G4
G5
G6
G7
G8
RELAY 11
G9
G10
G11
G12
G13
G14
G15
G16
G17
G18
E3
E4
E7
E8
E11
E12
E15
E16
Title:
EXT. CONN. DIAG: FEEDER PROT. RELAY (60TE) DIRECTIONAL
PHASE O/C & E/F WITH AUTO-RECLOSE (16 I/P & 18 O/P)
Drg
No:
10P14307
(STAFFORD)
DEFAULT SETTING
CUSTOMER SETTING
R1 IN/ISEF>Start
R2 I> Start
R3 Prot'n Trip
R4 General Alarm
R5 CB Fail Tmr 1
R6 Cntl CB Close
R7 Cntl CB Trip
R8 Any Start
R9 AR Successful
RELAY 10
R10 Non Auto
R11 AR In Prog
RELAY 12
R12 AR Lockout
RELAY 13
R13 ARInService
RELAY 14
R14 Live Line
RELAY 15
R15 Not Used
RELAY 16
R16 Not Used
RELAY 17
R17 Not Used
RELAY 18
R18 Not Used
2
Sht:
Next
Sht:
-

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents