Chapter 18 - Communications
P14x
Start
FirstTime = True
Read status word from
register 3x0001
FirstTime = True
Is disturbance bit
(bit 4) set?
No
Yes
Select next oldest non-
Yes
Is FirstTime =
extracted record by writing
True?
0x04 to register 4x00400
No
FirstTime = False
Send command to accept
Error
and select next record by
FirstTime = True
Extract disturbance record
writing 0x0C to register
4x00400
V01005

Figure 205: Automatic selection of disturbance record - method 2

7.4.6.3
EXTRACTING THE DISTURBANCE DATA
The extraction of the disturbance record is a two-stage process that involves extracting the configuration file first
and then the data file. first the configuration file must be extracted, followed by the data file: