Application Notes; Busbar Blocking Scheme; Figure 73: Blocked Earth Fault Logic; Figure 74: Simple Busbar Blocking Scheme - GE MiCOM P40 Agile Technical Manual

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14x
CB Fail Alarm
Remove IN> Start
Enabled
Disabled
IN1>1 Start
IN1>2 Start
IN1>3 Start
IN1>4 Start
IN2>1 Start
IN2>2 Start
IN2>3 Start
IN2>4 Start
ISEF>1 Start
ISEF>2 Start
ISEF>3 Start
ISEF>4 Start
V00649

Figure 73: Blocked Earth Fault logic

The IN/SEF>Blk Start signal is derived from the logical OR of the phase overcurrent start outputs. This output is
then gated with the CB Fail Alarm DDB signal and the Remove IN> Start setting.
14.4

APPLICATION NOTES

14.4.1

BUSBAR BLOCKING SCHEME

E00636

Figure 74: Simple busbar blocking scheme

P14xEd1-TM-EN-1
&
&
1
IED
O/P
CB
from
fail
start
backtrip
contact
Feeder 1
Feeder 2
Chapter 6 - Current Protection Functions
1
Incomer
IED
Block highset element
CB fail backtrip
IED
IED
Feeder 3
IN/SEF>Blk Start
IED
Feeder 4
147