DNGP Leak Test Procedure

1. Switch DNGP to standby from auto. Observe feedback mA indicator. If position of the valve changes follow
continue to step #2.
2. Move MCV to manual to close block valve or close cylinder block valves.
3. Check cylinder for decaying or equalizing pressure.
a) If cylinder pressure is decaying, check and repair leaks at fittings.
b) If cylinder pressure is equalizing, rebuild cylinder.
4. Check for external leak at gasket, NPT instrumentation ports.
a) If leak is found, tighten bolts or fittings.
b) If no leak is found, rebuild solenoid valve with O-ring kit by replacing lower valve body. See spare parts list
Table 12 for part numbers.