Setting Guidelines For High Impedance Operation; Figure 100: Hi-Z Ref Protection For Autotransformer Configuration - GE MiCOM P40 Agile Technical Manual

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 7 - Restricted Earth Fault Protection
CTN
V00686

Figure 100: Hi-Z REF Protection for autotransformer configuration

4.3.2

SETTING GUIDELINES FOR HIGH IMPEDANCE OPERATION

This scheme is very sensitive and can protect against low levels of fault current in resistance grounded systems. In
this application, the IREF>Is settings should be chosen to provide a primary operating current less than 10-25% of
the minimum earth fault level.
This scheme can also be used in a solidly grounded system. In this application, the IREF>Is settings should be
chosen to provide a primary operating current between 10% and 60 % of the winding rated current.
The following diagram shows the application of a high impedance REF element to protect the LV winding of a
power transformer.
178
CT1
A
B
C
Varistor
CT2
TN1 CT
Rst
P14xEd1-TM-EN-1
P14x
a
b
c