GE MiCOM P40 Agile Technical Manual page 618

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

CUSTOMER SETTING
DEFAULT SETTING
L1 Setting Group
L2 Setting Group
L3 Block IN1>3&4
L5 Rst LEDs/Lckt
NOTE:
3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO ENSURE
CORRECT OPERATION OF THE PROTECTIVE RELAY.
Issue:
Revision:
DRAWING OUTLINE UPDATED . CID BLIN-8BHLDT
C
Date:
25/11/2010
Name:
W.LINTERN
CAD DATA 1:1 DIMENSIONS: mm
DO NOT SCALE
Date:
Chkd:
D1
-
OPTO 1
D2
+
D3
-
OPTO 2
D4
+
D5
-
OPTO 3
D6
+
D7
-
OPTO 4
L4 Block I>3&4
D8
+
D9
-
OPTO 5
D10
+
D11
-
OPTO 6
L6 External Trip
D12
+
D13
-
OPTO 7
L7 CB Healthy
D14
+
D15
-
OPTO 8
L8 52-B
D16
+
D17
COMMON
D18
CONNECTION
MiCOM P142
(PART)
Substation Automation Solutions
F11
F12
F13
F14
E1
E2
E3
E4
E5
SEE NOTE 3
E6
E7
E8
E9
E10
E11
E12
E13
E14
E15
E16
E17
E18
B3
B4
B7
B8
B11
B12
B15
B16
Title:
EXT. CONN. DIAG: FEEDER PROT. RELAY (40TE) DIRECTIONAL
PHASE O/C & E/F WITH AUTO-RECLOSE (8 I/P & 11 O/P)
Drg
ALSTOM GRID UK LTD
No:
10P14205
(STAFFORD)
WATCHDOG
CONTACT
WATCHDOG
CONTACT
DEFAULT SETTING
CUSTOMER SETTING
RELAY 1
R1 IN/ISEF>Start
RELAY 2
R2 I> Start
R3 Prot'n Trip
RELAY 3
RELAY 4
R4 General Alarm
RELAY 5
R5 CB Fail Tmr 1
RELAY 6
R6 Cntl CB Close
R7 Cntl CB Trip
RELAY 7
RELAY 8
R8 Not Used
RELAY 9
R9 Not Used
RELAY 10
R10 Not Used
RELAY 11
R11 Not Used
2
Sht:
-
Next
Sht:

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents