Changing The Settings - GE MiCOM P40 Agile Technical Manual

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14x
Setting
Sys Fn Links (Row 03)
...
VIEW RECORDS
Select Event [0...n]
Menu Cell Ref
Time & Date
...
MEASUREMENTS 1
IA Magnitude
IA Phase Angle
IB Magnitude
...
The first three column headers are common throughout much of the product ranges. However the rows within
each of these column headers may differ according to the product type. Many of the column headers are the
same for all products within the series. However, there is no guarantee that the addresses will be the same for a
particular column header. Therefore you should always refer to the product settings documentation and not make
any assumptions.
3.8

CHANGING THE SETTINGS

1.
Starting at the default display, press the Down cursor key to show the first column heading.
2.
Use the horizontal cursor keys to select the required column heading.
3.
Use the vertical cursor keys to view the setting data in the column.
4.
To return to the column header, either press the Up cursor key for a second or so, or press the Clear key
once. It is only possible to move across columns at the column heading level.
5.
To return to the default display, press the Up cursor key or the Clear key from any of the column headings. If
you use the auto-repeat function of the Up cursor key, you cannot go straight to the default display from
one of the column cells because the auto-repeat stops at the column heading.
6.
To change the value of a setting, go to the relevant cell in the menu, then press the Enter key to change the
cell value. A flashing cursor on the LCD shows that the value can be changed. You may be prompted for a
password first.
7.
To change the setting value, press the Up and Down cursor keys. If the setting to be changed is a binary
value or a text string, select the required bit or character to be changed using the horizontal cursor keys.
8.
Press the Enter key to confirm the new setting value or the Clear key to discard it. The new setting is
automatically discarded if it is not confirmed within 15 seconds.
9.
For protection group settings and disturbance recorder settings, the changes must be confirmed before
they are used. When all required changes have been entered, return to the column heading level and press
the Down cursor key. Before returning to the default display, the following prompt appears.
10.
Press the Enter key to accept the new settings or press the Clear key to discard the new settings.
P14xEd1-TM-EN-1
Column
Row
00
03
Third setting within first column
...
...
01
00
Second Column definition
01
01
First setting within second column
01
02
Second setting within second column
01
03
Third setting within second column
...
...
02
00
Third Column definition
02
01
First setting within third column
02
02
Second setting within third column
02
03
Third setting within third column
...
...
Update settings?
ENTER or CLEAR
Chapter 5 - Configuration
Description
77

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents