Testing; Test Mode - GE B30 Instruction Manual

Bus differential system, ur series
Hide thumbs Also See for B30:
Table of Contents

Advertisement

5.10 TESTING

5.10TESTING

PATH: SETTINGS
TESTING
 SETTINGS
 TESTING
The B30 provides a test facility to verify the functionality of contact inputs and outputs, some communication channels and
the phasor measurement unit (where applicable), using simulated conditions. The test mode is indicated on the relay face-
plate by a Test Mode LED indicator.
The test mode may be in any of three states: disabled, isolated, or forcible.
In the "Disabled" mode, B30 operation is normal and all test features are disabled.
In the "Isolated" mode, the B30 is prevented from performing certain control actions, including tripping via contact outputs.
All relay contact outputs, including latching outputs, are disabled. Channel tests and phasor measurement unit tests remain
usable on applicable UR-series models.
In the "Forcible" mode, the operand selected by the
test mode is forcible, and the operand assigned to the
ate normally. If the test mode is forcible, and the operand assigned to the
tact inputs and outputs are forced to the values specified in the following sections. Forcing may be controlled by manually
changing the operand selected by the
ble pushbutton, contact input, or communication-based input operand. Channel tests and phasor measurement unit tests
5
remain usable on applicable UR-series models.
Communications based inputs and outputs remain fully operational in test mode. If a control action is programmed
using direct inputs and outputs or remote inputs and outputs, then the test procedure must take this into account.
NOTE
When in "Forcible" mode, the operand selected by the
testing conditions. To force contact inputs and outputs through relay settings, set
tact inputs and outputs through a user-programmable condition, such as FlexLogic™ operand (pushbutton, digital input,
communication-based input, or a combination of these), set
or output is forced when the selected operand assumes a logic 1 state.
The B30 remains fully operational in test mode, allowing for various testing procedures. In particular, the protection and
control elements, FlexLogic™, and communication-based inputs and outputs function normally.
The only difference between the normal operation and the test mode is the behavior of the input and output contacts. The
contact inputs can be forced to report as open or closed or remain fully operational, whereas the contact outputs can be
forced to open, close, freeze, or remain fully operational. The response of the digital input and output contacts to the test
mode is programmed individually for each input and output using the force contact inputs and force contact outputs test
functions described in the following sections.
The test mode state is indicated on the relay faceplate by a combination of the Test Mode LED indicator, the In-Service LED
indicator, and by the critical fail relay, as shown in the following table.
5-182

TEST MODE

TEST MODE
FUNCTION: Disabled
TEST MODE FORCING:
MESSAGE
On
TEST MODE FORCING
TEST MODE FORCING
B30 Bus Differential System
Range: Disabled, Isolated, Forcible
Range: FlexLogic™ operand
setting controls the relay inputs and outputs. If the
setting is "Off", the B30 inputs and outputs oper-
TEST MODE FORCING
TEST MODE FORCING
setting between on and off, or by selecting a user-programma-
setting dictates further response of the B30 to
TEST MODE FORCING
TEST MODE FORCING
to the desired operand. The contact input
TEST MODE FORCING
5 SETTINGS
5.10.1 TEST MODE
setting is "On", the B30 con-
to "On". To force con-
GE Multilin

Advertisement

Table of Contents
loading

Table of Contents