Cb Control Logic; Synchronisation Check; Cb Healthy Check; Figure 166: Cb Control Logic - GE MiCOM P40 Agile Technical Manual

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 14 - Monitoring and Control
7.6

CB CONTROL LOGIC

CB Control
Disabled
Local
Remote
Local+Remote
Opto +Rem+Local
HMI Trip
Init Trip CB
Init close CB
HMI Close
AR In Progress
Auto Close
AR models only
Reset Close Dly
Trip Command In
Ext. Trip 3ph
Control Trip
CB Open 3 ph
CB Closed 3 ph
CB Healthy
Voltage models only
Man Check Synch
V01208

Figure 166: CB Control logic

7.7

SYNCHRONISATION CHECK

Where the check synchronism function is set, this can be enabled to supervise manual circuit breaker Close
commands. A circuit breaker Close command will only be issued if the Check Synchronisation criteria are satisfied.
A time delay can be set with the setting Sys Check time. If the Check Synchronisation criteria are not satisfied
within the time period following a Close command the device will lockout and alarm.
7.8

CB HEALTHY CHECK

A CB Healthy check is available if required. This facility accepts an input to one of the opto-inputs to indicate that
the breaker is capable of closing (e.g. that it is fully charged). A time delay can be set with the setting CB Healthy
Time. If the CB does not indicate a healthy condition within the time period following a Close command, the device
will lockout and alarm.
328
Opto
Opto+Local
1
Opto +Remote
1
&
&
&
1
&
1
1
Enable opto -initiated CB trip and close
S
Q
R
Delayed control close time
S
Q
&
R
1
1
CB healthy window
&
C/S window
&
&
Close pulse
S
Q
Pulsed output latched in HMI
R
&
1
Man CB Unhealthy
Man No Checksync
P14xEd1-TM-EN-1
P14x
Control Trip
Man CB Trip Fail
Close in Prog
Control Close
CB Cls Fail

Hide quick links: