General; Ratings; Basic Impulse Level (Bil); Dielectric Test Voltage - GE CR194 Installation Instructions Manual

Two- '9 h. h vacuum limitamp control
Hide thumbs Also See for CR194:
Table of Contents

Advertisement

General

The basic CR194 two-high vacuum Limitamp® con trol­
ler is a fron t connected assembly of components and
conductors for motor starting, arranged in a conve­
nient two-high vertical stack. The enclosure allows
space and facilities for motor cable termination, plus
safety interlocking of doors and isolation switch to pre­
vent inadvertent en trance to high-voltage parts. U nless
specified otherwise, the motor cable barriers are in­
s talled for bottom motor cable entry, but are easily
field converted from bottom to top or top to bottom
motor cable entry. Removable conduit cutout covers
are provided in both the top & bottom ( if a bottom is
provided) for bringing in motor cable & control wir­
ing. In an effort to provide for maximum motor cable
access in the compact 36"-wide two-high design, in­
coming power cable must be connected in a separate
cable en trance compartment or the two-high must be
bus connected to existing equipment. No back access
is required, although both back and side access is pos­
sible by removal of back and side panels. The equip­
ment may be rated up to 5.0 kV.
In general, the starters in both the top and the bottom
are divided into high-voltage and low-voltage
compartments, separated by doors and barriers.
Mounted on the high-voltage door of each s tarter is
the low-voltage control cavity, with the low voltage
door hinged to the high-voltage door. Access to the
low voltage panel is obtained by rotating the two Y4
turn latches on the low-voltage door, the n opening the
door to the left. To open the high-voltage door, the
power must be disconnected by a sequence of
manual operations which requires de-energizing the
high-voltage contactor, operating the isolation switch
handle by rotating it downward, loosening the two
latch bolts on the high-vol tage door, then opening the
door to the left. Low-vol tage doors may be entered
without disconnecting the power, but this should be
done with caution.
Installation, operation and maintenance should be
performed only by experienced personnel trained in
this class of equipment.

Ratings

Refer to the panel data nameplate (see Figure 4) on
the fron t of the enclosure for detailed ratings appli­
cable to a particular controller. Equipment basic rat­
ings equal or exceed NEMA ICS 3, Part 2 for Class E2
Controllers, and are summarized below.
&
Starter Main Bus
Maximum Current Ratings
Main Bus
I Bar/
Enclosure Type
Phase
Vented
1200A
Non-Vented
1200A
Starter Max.
Current
2 Bars/
Top
Bottom
Phase
Unit
Unit
2000A
360A
400A
320A
1950A
320A
CR194 Two-High Vacuum Limitamp® Control
OPERATING
HANDLE
HANDLE ---- -. .. .. .:.:
OPERATING
INSTRUCTIONS
PANEL
DATA
NAMEPLATE
4.
Figure
Operating handle, handle operating instructions
and panel data nameplate
Interrupting Ratings At Utilization Voltage Shown
Maximum
Maximum
Continuous
Volts
Amperes(RMS)
2500
400
3600
400
5000
400

Basic Impulse Level (BIL)

The standard BIL rating of vacuum Limitamp® con­
trollers is 60kV crest (design rating) . This rating ex­
cludes dry-type control transformers and starting reac­
tors & autotransformers.

Dielectric Test Voltage

21/t times nameplate voltage plus 2000 volts.

High-Voltage Vacuum Contactors

The vacuum contactors used in vacuum Limitamp®
controllers are available in two different ratings: 400
and 800 amperes. This publication covers only the 400
ampere rating as used in CR194 two-high vacuum
Limitamp®. The 400 ampere and 800 ampere
con tactors are similar in operation but very different
� ... �·,·-· "''"'
--
'
, ... , .. , ,_,_,
....
Three-phase Symmetrical
Class E l
Class E2
Fused
Unfused
25
200
37
300
50
400