GE MiCOM P40 Agile Technical Manual page 631

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

DIRECTION OF FORWARD CURRENT FLOW
P2
P1 P2
S2
S1
S2
S1
B
C
A
NOTE 2
N
n
a
b c
NOTES 1.
C.T. SHORTING LINKS
(a)
(b)
PIN TERMINAL (P.C.B. TYPE)
2. C.T. CONNECTIONS ARE SHOWN 1A CONNECTED AND ARE TYPICAL ONLY.
Issue:
Revision:
FIELD VOLTAGE OUTPUT REMOVED. CID HONG-95RDV7
E
Date:
18/04/2013
Name:
H.ONG
CAD DATA 1:1 DIMENSIONS: mm
DO NOT SCALE
Date:
Chkd:
P1
MiCOM P143 (PART)
C1
5A
A
C2
1A
C3
C4
5A
B
C5
1A
C6
C7
5A
C
C8
1A
C9
C10
5A
N
C11
1A
C12
C13
5A
N
SENSITIVE
C14
1A
C15
A
C19
B
C20
C
C21
N
C22
3. THIS RELAY SHOULD BE ASSIGNED TO ANY TRIP TO
ENSURE CORRECT OPERATION OF THE PROTECTIVE RELAY.
4. FOR COMMS OPTIONS SEE DRAWING 10Px4001.
Substation Automation Solutions
A
X
A
X
B
X
C
C
A
B
C
PHASE ROTATION
N
n
a
c
b
C23
V CHECK
SYNC
C24
D1
-
OPTO 1
D2
+
D3
-
OPTO 2
D4
+
D5
-
OPTO 3
D6
+
D7
-
OPTO 4
D8
+
D9
-
OPTO 5
D10
+
D11
-
OPTO 6
D12
+
D13
-
OPTO 7
D14
+
D15
-
D16
OPTO 8
+
D17
COMMON
D18
CONNECTION
Title:
EXT. CONN. DIAG: FEEDER PROT. RELAY (60TE) DIRECTIONAL
PHASE O/C & E/F WITH AUTO-RECLOSE (16 I/P & 18 O/P)
Drg
ALSTOM GRID UK LTD
No:
10P14307
(STAFFORD)
MiCOM P143 (PART)
F1
OPTO 9
F2
B
F3
OPTO 10
F4
F5
OPTO 11
F6
F7
OPTO 12
F8
F9
OPTO 13
F10
F11
OPTO 14
F12
F13
OPTO 15
F14
F15
OPTO 16
F16
F17
COMMON
F18
CONNECTION
COMMS
NOTE 4
J17
-
SEE DRAWING
EIA485/
10Px4001.
KBUS
J18
PORT
+
J16
SCN
*
J1
-
AC OR DC
x
J2
AUX SUPPLY
+
CASE
EARTH
POWER SUPPLY VERSION 24-48V (NOMINAL) D.C. ONLY
*
Sht:
Next
Sht:
J11
WATCHDOG
J12
CONTACT
J13
WATCHDOG
J14
CONTACT
H1
RELAY 1
H2
H3
RELAY 2
H4
H5
RELAY 3 ANY TRIP
H6
NOTE 3
H7
H8
RELAY 4
H9
H10
H11
RELAY 5
H12
H13
H14
RELAY 6
H15
H16
H17
RELAY 7
H18
G1
RELAY 8
G2
G3
RELAY 9
G4
G5
RELAY 10
G6
G7
G8
RELAY 11
G9
G10
G11
RELAY 12
G12
G13
G14
RELAY 13
G15
G16
G17
RELAY 14
G18
E3
RELAY 15
E4
E7
RELAY 16
E8
HIGH BREAK
E11
CONTACTS
RELAY 17
E12
E15
RELAY 18
E16
1