GE MiCOM P40 Agile Technical Manual page 448

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Chapter 18 - Communications
Models Covered:
Highest DNP Level Supported*:
*This is the highest DNP level FULLY supported. Parts of level 3 are
also supported
Device Function:
Notable objects, functions, and/or qualifiers supported in addition to the highest DNP levels supported (the complete list is described in the
DNP 3.0 Implementation Table):
For static (non-change event) object requests, request qualifier codes 00 and 01 (start-stop), 07 and 08 (limited quantity), and 17 and 28 (index)
are supported in addition to the request qualifier code 06 (no range (all points))
Static object requests sent with qualifiers 00, 01, 06, 07, or 08 will be responded with qualifiers 00 or 01
Static object requests sent with qualifiers 17 or 28 will be responded with qualifiers 17 or 28
For change-event object requests, qualifiers 17 or 28 are always responded
16-bit and 32-bit analogue change events with time may be requested
The read function code for Object 50 (time and date) variation 1 is supported
Analogue Input Deadbands, Object 34, variations 1 through 3, are supported
Floating Point Analogue Output Status and Output Block Objects 40 and 41 are supported
Sequential file transfer, Object 70, variations 2 through 7, are supported
Device Attribute Object 0 is supported
Maximum Data Link Frame Size (octets):
Maximum Application Fragment Size (octets)
Maximum Data Link Retries:
Maximum Application Layer Retries:
Requires Data Link Layer Confirmation:
Requires Application Layer Confirmation:
Timeouts while waiting for:
Data Link Confirm:
Complete Application Fragment:
Application Confirm:
Complete Application Response:
Others:
Data Link Confirm Timeout:
Application Confirm Timeout:
Select/Operate Arm Timeout:
Need Time Interval (Set IIN1-4):
Application File Timeout
Analog Change Event Scan Period:
Counter Change Event Scan Period
Frozen Counter Change Event Scan Period
Maximum Delay Measurement Error:
Time Base Drift Over a 10-minute Interval:
Sends/Executes Control Operations:
Write Binary Outputs:
Select/Operate:
422
DNP 3.0
Device Profile Document
All models
For Requests: Level 2
For Responses: Level 2
Slave
Transmitted: 292
Received: 292
Transmitted: Configurable (100 to 2048). Default 2048
Received: 249
Fixed at 2
None
Configurable to Never or Always
When reporting event data (Slave devices only)
When sending multi-fragment responses (Slave devices only)
Configurable
None
Configurable
None
Configurable from 0 (Disabled) to 120s, default 10s.
Configurable from 1 to 120s, default 2s.
Configurable from 1 to 10s, default 10s.
Configurable from 1 to 30, default 10min.
60 s
Fixed at 0.5s
Fixed at 0.5s
Fixed at 1s
2.5 ms
7 ms
Never
Always
P14x
P14xEd1-TM-EN-1