Figure 101: High Impedance Ref For The Lv Winding - GE MiCOM P40 Agile Technical Manual

Feeder management ied
Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P14x
A
B
C
Transformer:
Buderns:
R
R
V00687

Figure 101: High Impedance REF for the LV winding

4.3.2.1
STABILITY VOLTAGE CALCULATION
The transformer full load current, IFLC, is:
6
I
= (90 x 10
) / (132 x 103 x
FLC
To calculate the stability voltage the maximum through fault level should be considered. The maximum through
fault level, ignoring the source impedance, I
I
= I
/ X
= 394 / 0.05 = 7873 A
F
FLC
TX
The required stability voltage, VS, and assuming one CT saturated is:
V
= KI
(R
+ 2R
s
F
CT
The following figure can be used to determine the K factor and the operating time. The K factor is valid when:
5 ≤ X/R ≤ 120
and
0.5In ≤ I f ≤ 40In
We recommend a value of VK/VS = 4.
With the transformer at full load current and percentage impedance voltage of 394A and 5% respectively, the
prospective fault current is 7873 A and the required stability voltage Vs (assuming that one CT is saturated) is:
V
= 0.9 x 7873 x (0.5 + 2 x 0.98) / 400 = 45.5 V
s
The CTs knee point voltage should be at least 4 times Vs so that an average operating time of 40 ms is achieved.
4.3.2.2
PRIMARY CURRENT CALCULATION
The primary operating current should be between 10 and 60 % of the winding rated current. Assuming that the
relay effective setting or primary operating current is approximately 30% of the full load current, the calculation
below shows that a setting of less than 0.3 A is required.
Effective setting = 0.3I
P14xEd1-TM-EN-1
90 MVA
33/132 kV
Dyn11, X = 5%
= 0.5 W
CT
= 0.98 W
L
Ö 3) = 394 A
, is:
F
)
L
/ CT Ratio = 30.3 x 394 / 400 = approximately 0.3 A
FLC
Chapter 7 - Restricted Earth Fault Protection
R
L
R
L
High Z
R
CT
REF
R
L
400:1
a
R
CT
b
c
R
L
179

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents