Got Side Settings; Communication Detail Settings - Mitsubishi Electric GOT1000 Series Connection Manual

Microcomputers, modbus products, peripherals
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

*1
Click the [Setting] button and perform the setting in the [GOT
IP Address Setting] screen.
*2
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
5.3.3 Ethernet setting
(2) GT15, GT12
Item
Description
Set the network No. of the GOT.
GOT NET No.
(Default: 1)
GOT PLC
Set the station No. of the GOT.
*1
(Default: 1)
No.
GOT
Set the IP address of the GOT.
IP Address
(Default: 192.168.0.18)
Set the subnet mask for the sub
network.(Only for connection via
router)
Subnet Mask
If the sub network is not used, the
default value is set.
(Default: 255.255.255.0)
Set the router address of the
default gateway where the GOT is
Default
connected.(Only for connection via
Gateway
router)
(Default: 0.0.0.0)
Ethernet
Set the GOT port No. for Ethernet
Download Port
download.
No. *2 *3
(Default: 5014)
Set the GOT port No. for the
GOT
connection with the Ethernet
Communication
module.
Port No.
(Default: 5020)
5 - 4
5. MODBUS(R)/TCP CONNECTION

5.3 GOT Side Settings

Startup Time
Timeout Time
Delay Time
32bit Storage
POINT
POINT
POINT
Range
1 to 239
1 to 247
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
0.0.0.0 to
255.255.255.255
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
1024 to 5010,
5014 to 65534
(Except for 5011,
5012, 5013 and
49153)
Item
Description
Specify the time period from the
GOT startup until GOT starts the
communication with the PLC CPU.
(Default: 3sec)
Set the time period for a
communication to time out.
(Default: 3sec)
Set the delay time for reducing the
load of the network/destination
PLC.
(Default: 0ms)
Select the steps to store two words
(32-bit data).
(Default: LH Order)
*1
Each of [GOT PLC No.] set in the communication detail
setting and [PLC No.] set in the Ethernet setting must be set
to different station numbers.
5.3.3 Ethernet setting
(1) Communication interface setting by the Utility
The communication interface setting can be
changed on the Utility's [Communication setting]
after writing [Communication Settings] of project
data.
For details on the Utility, refer to the following
manual.
User's Manual of GOT used.
(2) Precedence in communication settings
When settings are made by GT Designer3 or the
Utility, the latest setting is effective.
Range
3 to 255sec
3 to 90sec
0 to 10000
(
10 ms)
LH Order/HL Order