(1) Modbus Communication Portfolio License
To set the communication settings for STARDOM, an installation of Modbus Communication Portfolio License is
required.
For details of the communication settings, refer to the following manual.
STARDOM FCN/FCJ Guide
(2) Defining Logic POU
Define Logic POU using Logic Designer (peripheral software), and download the project to STARDOM.
(a) Start Logic Designer and create a new project using a template.
Use [STARDOM Serial Communication] template.
(b) Insert Firmware Library to the new project.
• Right-click [Library] under the project tree in Logic Designer.
• Right-click [Insert] and select [Firmware Library].
• Double-click the [SD_FCXPLCE_LIB] folder and double-click [SD_FCXPLCE_LIB.fwl] to select it.
• The library path inserted in the procedures above is as follows.
{Install Folder}\LogicDesigner\Mwt\Plc\Fw_lib\SD_FCXPLCE_LIB\SD_FCXPLCE_LIB.fwl
(c) Insert User Library to the new project.
• Right-click [Library] under the project tree in Logic Designer.
• Right-click [Insert] and select [User Library].
• Double-click [SD_CMODBUSE_PF.mwt], [SD_CUTIL_PF.mwt] and [SD_CMODBUSS_PF.mwt] to
select it.
(When [STARDOM Serial Communication] is used for the template, [SD_CUTIL_PF.mwt] is inserted as
default.)
• The library path inserted in the procedures above is as follows.
{Install Folder}\LogicDesigner\Libraries\SD_CMODBUSE_PF.mwt
{Install Folder}\LogicDesigner\Libraries\SD_CUTIL_PF.mwt
{Install Folder}\LogicDesigner\Libraries\SD_CMODBUSS_PF.mwt
(d) Copy a sample project POU to the new project.
• Open "SD_CMODBUSE_Sample1.mwt".
• Right-click [ComEServerModbus*] in the Logic POU under the project tree in the
SD_CMODBUSE_Sample1 project, and select [Copy].
• Right-click the [Logic POU] under the project tree in the previously created project, and select [Paste].
• Double-click the [ComEServerModbus*] file in the [ComEServerModbus*] folder.
• For the following terminals, set as shown below.
5. MODBUS(R)/TCP CONNECTION
5.6 Example of Connection