Connectable Model List; System Configuration; Connecting To Modbus(R)/Tcp Equipment - Mitsubishi Electric GOT1000 Series Connection Manual

Microcomputers, modbus products, peripherals
Hide thumbs Also See for GOT1000 Series:
Table of Contents

Advertisement

5.
MODBUS(R)/TCP CONNECTION

5.1 Connectable Model List

GOT1000 Series products support the master function of MODBUS
Thus, the GOT can be connected with each MODBUS
For applicable MODBUS

5.2 System Configuration

5.2.1

Connecting to MODBUS(R)/TCP equipment

®
MODBUS
/TCP
equipment
Commun
Controller
ication
Cable model
Type
Twisted pair cable
• 10BASE-T
Shielded twisted
pair cable (STP) or
®
MODBUS
unshielded twisted
Ethernet
/TCP
pair cable (UTP):
equipment
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
*1
Connect the GOT to the MODBUS
Use cables, connectors, and hubs that meet the IEEE802.3 10BASE-T/100BASE-TX standards.
*2
When connecting GT16 to an equipment that meets the 10BASE (-T/2/5) standard, use the switching hub and operate in an
environment where 10Mbps and 100Mbps can be mixed.
*3
A length between a hub and a node.
The maximum distance differs depending on the Ethernet device to be used.
The following shows the number of the connectable nodes when a repeater hub is used.
• 10BASE-T: Max. 4 nodes for a cascade connection (500m)
• 100BASE-TX: Max. 2 nodes for a cascade connection (205m)
When switching hubs are used, the cascade connection between the switching hubs has no logical limit for the number of
cascades.
For the limit, contact the switching hub manufacturer.
*4
Use the straight cable.
*5
For details, refer to the MODBUS
*6
GT14 models compatible with Ethernet connection are only GT1455-QTBDE, GT1450-QMBDE and GT1450-QLBDE.
5 - 2
5. MODBUS(R)/TCP CONNECTION

5.1 Connectable Model List

®
/TCP equipment, refer to the following Technical News.
List of Valid Devices Applicable for GOT1000 Series with MODBUS Connection (GOT-A-0037)
Connection cable
Connection cable
External
Maximum
device
segment
*3
length
*4
100m
Hub
®
/TCP equipment via a hub.
®
/TCP equipment manual.
®
/TCP communication, the open FA network.
®
/TCP slave.
Hub
Connection cable
Connection cable
Maximum
segment
Cable model
length
*4
Twisted pair cable
• 10BASE-T
Shielded twisted
pair cable (STP) or
unshielded twisted
*1
pair cable (UTP):
Category 3, 4, and 5
• 100BASE-TX
Shielded twisted
pair cable (STP):
Category 5 and 5e
GOT
*2
GOT
Option
GOT
device
model
*3
- (Built into
*6
GOT)
100m
GT15-
J71E71-
100
Number of connectable
equipment
When controller:GOT
is N:1
The following shows
the number of
controllers for 1 GOT
<For GT16, GT14>
TCP: 128 or less
<For GT15, GT12>
TCP: 10 or less
When controller:GOT
is 1:N
The following shows
the number of GOTs
for 1 controller
Depends on the
®
MODBUS
/TCP
*5
equipment used.

Advertisement

Table of Contents
loading