POINT
POINT
POINT
The polarity A and B in signal names may be reversed
depending on the microcomputer to be used.
Prepare a cable according to the microcomputer to be
used.
Precautions when preparing a cable
(1) Cable length
The distance between the GOT and the PLC of
connection diagram 1), 2) and 3) must be 1200 m or
less.
The length of the RS-422 connection diagram 4) or RS-
422 connection diagram 5) must be 30m or less.
(2) GOT side connector
For the GOT side connector, refer to the following.
1.4.1 GOT connector specifications
Connecting terminating resistors
(1) GOT side
When connecting a microcomputer to the GOT, a
terminating resistor must be connected to the GOT.
(a) For GT16, GT15, GT12
Set the terminating resistor setting switch of the
GOT main unit to "Disable".
(b) For GT14, GT11, GT10
Set the terminating resistor selector to "330 ".
For the procedure to set the terminating resistor, refer
to the following.
1.4.3 Terminating resistors of GOT