Dimensions Of Flue Gas Outlet Pipe; Length Of The Air And Flue Gas Pipes - REMEHA Quinta Pro 30 Installation, User And Service Manual

High-efficiency wall-hung gas boiler
Hide thumbs Also See for Quinta Pro 30:
Table of Contents

Advertisement

Fig.13
Dimensions of concentric connec­
tion
ød
1
øD
Fig.14
Room-ventilated version
Tab.15
Maximum length (L)
Diameter
Quinta Pro 30
Quinta Pro 45
Quinta Pro 55
Quinta Pro 65
Quinta Pro 90
Quinta Pro 115
123157 - v.12 - 07022018
1
AD-3000962-01
L
=
AD-0000028-02
6.5.3

Dimensions of flue gas outlet pipe

Warning
The pipes connected to the flue gas adapter must satisfy the fol­
lowing dimension requirements.
d
External dimensions of flue gas outlet pipe
1
D
External dimensions of air supply pipe
1
L
Length difference between flue gas outlet pipe and air supply pipe
1
Tab.14
Dimensions of pipe
d
(min-max)
1
80/125 mm
79.3 - 80.3 mm
100/150 mm
99.3 - 100.3 mm
(1) Shorten the inner pipe if the length difference is too great.
6.5.4

Length of the air and flue gas pipes

The maximum length of the flue gas outlet and air supply channel vary de­
pending on the appliance type; consult the relevant chapter for the correct
lengths.
Important
When using bends, the maximum chimney length (L) must be
shortened according to the reduction table.
For adaptation to another diameter use approved transitions
The boiler is also suitable for longer chimney lengths and diam­
eters other than those specified in the tables. Contact us for
more information.
Room-ventilated model (B
L Length of the flue gas outlet channel to roof feed-through
Connecting the flue gas outlet
Connecting the air supply
With a room-ventilated version, the air supply opening stays open; only the
flue gas outlet opening is connected. This will ensure that the boiler ob­
tains the necessary combustion air directly from the installation area.
Caution
The air supply opening must stay open.
The installation area must be equipped with the necessary air
supply openings. These openings must not be obstructed or
shut off.
80 mm
90 mm
33 m
40 m
39 m
40 m
(1)
16 m
26 m
11 m
17 m
10 m
16 m
8 m
13 m
D
(min-max)
L
1
124 - 125.5 mm
0 - 15 mm
149 - 151 mm
0 - 15 mm
)
23P
100 mm
110 mm
40 m
40 m
(1)
(1)
40 m
40 m
(1)
(1)
39 m
40 m
(1)
26 m
40 m
24 m
40 m
19 m
38 m
6 Installation
(min-max)
(1)
1
130 mm
(1)
40 m
(1)
40 m
(1)
40 m
(1)
40 m
(1)
40 m
(1)
40 m
(1)
27