ELEcTrIcAL INSTALLATION

6.7.2 Temperature detection T1b, T2b

Parameter In.17 displays the function of the used temperature input in the first digit
of the hex value. The KEB COMBIVERT is delivered as standard with a switchable
PTC / KTY evaluation. The required function is set with Pn.72 (dr33 at F6) and operates
according to the following table:
Function of T1x,
In.17
T2x
(Hex)
KTY84
5xh
PTC
(in accordance with
DIN EN 60947-8)
6xh
PT100
Table 3:
Temperature detection
The column is valid at factory setting. The function must be parameterized appropriate with parame-
1)
ters Pn.12, Pn.13, Pn.62 and Pn.72 for F5 in operating mode GENERAL.
2)
The switch-off is dependent on the adjusted temperature in Pn.62 (F6 => Pn11 / 14).
Depending on the application, the temperature input can be used for the following func-
tions:
Function
Motor temperature display and monitoring
Motor temperature monitoring
Temperature control for liquid-cooled motors
General fault sensing
Table 4:
Functions temperature input
1)
If the temperature input is required for other functions, the motor temperature control can also occur
indirectly via the coolant circuit of the inverter.
62
Pn.72
resistance
(dr33)
< 215 Ω
498 Ω
0
1 kΩ
1.722 kΩ
> 1811 Ω
< 750 Ω
0.75...1.65 kΩ
(reset resistance)
1
1.65...4 kΩ
(tripping resistance)
> 4 kΩ
The behaviour of the inverter in case of error / warning is defined with param-
eter Pn.12 (CP.28), Pn.13 (F6 => Pn12 / 13).
1)
Display ru.46
(F6 => ru28)
Detection error 253
1°C
100°C
200°C
Detection error 254
T1x-T2x closed
undefined
undefined
T1x-T2x open
upon request
Mode (F5 => Pn.72; F6 => dr33)
KTY84
PTC
KTY84
PTC
Error/warn-
ing
1)
yes
no
2)
yes
2)
yes
2)
yes
no
yes