ANNEx - cOOLING SYSTEM
c.1.9 Volume flow depending on total power dissipation and temperature difference
8,0
7,5
7,0
6,5
6,0
5,5
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
20
22
24
26
Legend
①
–––––
90 l/min
③
–––––
110 l/min
⑤
–––––
130 l/min
Recommended working range
Figure 45:
Volume flow depending on total power dissipation and temperature difference
ATTENTION
88
28
30
32
34
36
38
Total power dissipation Pv in kW
Total volume flow
•
The minimum volume flow is dependent on the total power dissipa-
tion. This can be found in the technical data.
•
The resulting volume flow has to be in the recommended operating
range of the temperature difference.
•
Maximum temperature difference (ΔT) between flow and return
flow 6 K.
•
A volume flow above 140 l/min increases the risk of erosion in the
cooling system.
•
A discontinuous mode is not permissible.
•
Pay attention to flux direction and check tightness.
①
40
42
44
46
48
50
②
–––––
100 l/min
④
–––––
120 l/min
⑥
–––––
140 l/min
②
③
④
⑤
⑥
52
54
56
58
60