MEcHANIcAL INSTALLATION

5.5 Installation location requirements

90°
Figure 16:
Align the control cabinet system

5.5.1 Information about the service life

48
Alignment in balance.
► Check the ground with a water level.
► Align the cabinet system at a 90° angle to the ground.
The installation location must be free from dirt and moisture.
The surface must be as flat as possible and must be able to carry the weight of the
cabinet system.
The cabinet system must be installed in upright position.
Before installation, check the ground by means of a water-gauge.
Possible unevennesses at the installation location can be compensated with level-
ling feet.
Install the cabinet system on a solid, vibration-free ground.
Screw the cabinet system in the final position.
Provide sufficient air exchange to dissipate the resulting heat loss.
Avoid environmental influences such as high temperatures and high humidity, as
well as dust, dirt and aggressive gases.
Prevent moisture condensation within the cabinet system.
90°