ANNEx - cOOLING SYSTEM

c Annex - cooling System
c.1 General information
Since a liquid cooling is used for the cabinet system, the used components can be oper-
ated significantly cooler in continuous operation than in air-cooled cabinet systems. This
has positive effects on the lifetime of components such as fans, DC link capacitors and
power modules (IGBT). Also the temperature dependent switching losses are positively
effected. For applications with process-related coolants the use of water-cooled cabinet
systems is recommended.
ATTENTION
c.1.1 Materials in the cooling cicuit
For all metallic elements which are in contact with the cooling liquid (electrolyte) in the
cooling circuit, select a material which forms a small voltage difference to the heat sink
(see electrochemical voltage series). This prevents the formation of contact corrosion
and / or pitting.
Electro-chemical voltage series / standard potentials against hydrogen
Material
Generated Ion
Lithium
Li
Potassium
K
Calcium
Ca
Sodium
Na
Magnesium
Mg
Titan
Ti
Aluminium
Al
Manganese
Mn
Zinc
Zn
Chrome
Cr
Iron
Fe
Cadmium
Cd
Cobald
Co
Table 11:
Electro-chemical voltage series
Observe maximum operating pressure.
► In order to avoid a deformation of the used components and the
damages thereby, the indicated max. operating pressure may not be
exceeded briefly also by pressure peaks.
► Pay attention to the guidelines 97/23/EG of pressure units.
Standard poten-
tial
-3.04 V
+
-2.93 V
+
-2.87 V
2+
-2.71 V
+
-2.38 V
2+
-1.75 V
2+
-1.67 V
3+
-1.05 V
2+
-0.76 V
2+
-0.71 V
3+
-0.44 V
2+
-0.40 V
2+
-0.28 V
2+
We recommend the use of stainless steel or nickel plated brass cable glands.
Material
Generated Ion
Nickel
Ni
Tin
Sn
Lead
Pb
Iron
Fe
Hydrogen
2H
Stainless steel
diverse
Copper
Cu
Carbon
C
2+
Silver
Ag
Platinum
Pt
Gold
Au
Gold
Au
Standard poten-
tial
-0.25 V
2+
-0.14 V
2+
-0.13 V
3+
-0.037 V
3+
0.00 V
+
0.2...0.4 V
0.34 V
2+
0.74 V
0.80 V
+
1.20 V
2+
1.42 V
3+
1.69 V
+
83