ELEcTrIcAL INSTALLATION

6.5.3 Instructions for installation

We recommend the use of Lappkabel Ölflex Classic 100.
► Remove the upper insulation of the connection cables over a length of 43 cm, this
► Cut the rubber sleeve of the cable entry at 46 mm - 52 mm to ensure a clean seal.
► Connect the connection cables through the rubber sleeves in the control cabinet.
► Strip the cable for the front level to 30 mm, for the rear to 55 mms.
► Use wire-end ferrules for flexible and highly flexible conductors.
► The order of the three phases viewed from the left is L3, L2, L1 => Figure 23.
► The tightening torque of the tunnel terminal is 31 Nm.
► Connect the PE cables to the earthing bar with the supplied Rittal connection termi-
recommended mains cable type
PE
U
V
PE
PE
W
Other possible mains cable types
U
V
PE
W
U
V
PE
W
Figure 25:
Cross-section mains cable types
facilitates the entry into the cabinet.
nals (SV 3459 500 70-185 mm²).
Three-phase round core cable
with symmetrically distributed PE conductors
with reduced PE conductors
Compliance with the requirements according to EN 61439-1
Three-phase round core cable
without reduced PE conductor
Compliance with the requirements according to EN 61439-1
Three-phase round core cable
with reduced PE conductor
Compliance with the requirements according to EN 61439-1