Chapter 19 - Commissioning Instructions
6

SETTING CHECKS

The setting checks ensure that all of the application-specific settings (both the IED's function and programmable
scheme logic settings) have been correctly applied.
Note:
If applicable, the trip circuit should remain isolated during these checks to prevent accidental operation of the associated
circuit breaker.
6.1

APPLY APPLICATION-SPECIFIC SETTINGS

There are two different methods of applying the settings to the IED
Transferring settings to the IED from a pre-prepared setting file using MiCOM S1 Agile
Enter the settings manually using the IED's front panel HMI
6.1.1

TRANSFERRING SETTINGS FROM A SETTINGS FILE

This is the preferred method for transferring function settings. It is much faster and there is a lower margin for
error.
1.
Connect a PC running the Settings Application Software to the IED's front port, or a rear Ethernet port.
Alternatively connect to the rear Courier communications port, using a KITZ protocol converter if necessary.
2.
Power on the IED
3.
Enter the IP address of the device if it is Ethernet enabled
4.
Right-click the appropriate device name in the System Explorer pane and select Send
5.
In the Send to dialog select the setting files and click Send
Note:
The device name may not already exist in the system shown in System Explorer. In this case, perform a Quick Connect to the
IED, then manually add the settings file to the device name in the system. Refer to the Settings Application Software help for
details of how to do this.
6.1.2

ENTERING SETTINGS USING THE HMI

1.
Starting at the default display, press the Down cursor key to show the first column heading.
2.
Use the horizontal cursor keys to select the required column heading.
3.
Use the vertical cursor keys to view the setting data in the column.
4.
To return to the column header, either press the Up cursor key for a second or so, or press the Cancel key
once. It is only possible to move across columns at the column heading level.
5.
To return to the default display, press the Up cursor key or the Cancel key from any of the column headings.
If you use the auto-repeat function of the Up cursor key, you cannot go straight to the default display from
one of the column cells because the auto-repeat stops at the column heading.
6.
To change the value of a setting, go to the relevant cell in the menu, then press the Enter key to change the
cell value. A flashing cursor on the LCD shows that the value can be changed. You may be prompted for a
password first.
7.
To change the setting value, press the vertical cursor keys. If the setting to be changed is a binary value or a
text string, select the required bit or character to be changed using the left and right cursor keys.
412