Power Distribution Boards; Removing The Power Distribution Boards - Dell PowerEdge C6320p Owner's Manual

Hide thumbs Also See for PowerEdge C6320p:
Table of Contents

Advertisement

Steps
1.
Align the cooling fan cage with the locating pins on the chassis, and place it into the chassis until it is firmly seated.
2.
Guide the fan cage cable in from beneath the middle-wall bracket.
3.
Connect the fan's power cable to the connector on the power distribution board 1.
Route this cable properly through the cable tie to prevent the cable from being pinched or crimped.
Figure 89. Installing the cooling fan cage
Next steps
1.
Install the cooling fans.
2.
Follow the procedure listed in the After working inside your system section.
3.
Check the management software to see if all the fans are rotating at the optimal speed.
Related links
Safety instructions
Before working inside your system
Removing a cooling fan
Installing a cooling fan
After working inside your system

Power distribution boards

The power distribution board (PDB) is a board that connects the redundant power supply units to the system board. The Fan
Control Board is a part of the PDB1. A PDB is only available in systems that support redundant power supply units. This system has
two PDBs. The procedure to remove and install both the PDBs is similar. Remove PDB 1, to access PDB 2.

Removing the power distribution boards

Prerequisites
CAUTION: Many repairs may only be done by a certified service technician. You should only perform troubleshooting and
simple repairs as authorized in your product documentation, or as directed by the online or telephone service and support
team. Damage due to servicing that is not authorized by Dell is not covered by your warranty. Read and follow the safety
instructions that are shipped with your product.
1.
Follow the safety guidelines listed in the Safety instructions section.