ComAp InteliCompact NT Reference Manual page 277

Paralleling gen-set controller sw version 2.1
Hide thumbs Also See for InteliCompact NT:
Table of Contents

Advertisement

Alarm: Stop fail
Alarm type Shutdown
Stop fail
Alarmlist
message
Alarm
While the engine shall be stopped
evaluated
Related
All
applications
Description This alarm occurs if the gen-set shall be stopped, but some symptom indicates that it is
not stopped. The period when the gen-set shall be stopped begins after the fuel has
been switched off and time delay
fuel resp. starter motor are off.
STARTER
FUEL SOLENOID
See the chapter
account for the evaluation of stopped engine.
N
:
OTE
The gen-set cannot be started until this alarm is inactive and reset.
Alarm: RPM measurement failure
Alarm type
Warning
Sd RPMMeasFail
Alarmlist
message
Alarm evaluated
During cranking
Related
All
applications
Description
The alarm is issued if the engine speed has not exceeded the
within the
indication
NT
InteliCompact
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Stop time
ENGINE STOP
Stop time
Stop fail alarm is evaluated here
Cool down and stop
to learn more about symptoms that are taken into
MaxCrank
Time, although some of
sources indicate that the engine has started.
has elapsed and lasts for the entire time the
ENGINE START
Starting RPM
additional running engine
277