Group: Engine Params - ComAp InteliCompact NT Reference Manual

Paralleling gen-set controller sw version 2.1
Hide thumbs Also See for InteliCompact NT:
Table of Contents

Advertisement

Setpoint: Time Zone
Group
Comms Settings
GMT -12:00 ... GMT +13:00 [-]
Range [units]
Related
All
applications
Description
This setpoint is used to select the time zone where the controller is located.
Refer to your computer time zone settings (click on the time indicator located
in the rightmost position of the Windows task bar) if you are not sure about
your time zone.
H
:
INT
If the time zone is not selected properly the active e-mails may contain
incorrect information about the time they were sent, which may result in
confusion about when the respective problem actually occurred.
Setpoint: DNS IP Address
Group
Comms Settings
Range [units]
[-]
Related
All
applications
Description
If DHCP is DISABLED this setpoint is used to adjust the domain name
server (DNS), which is needed to translate domain names in e-mail
addresses and server names into correct IP addresses.
If DHCP is ENABLED this setpoint is used to display the DNS server
assigned by the DHCP server.

16.1.4 Group: Engine Params

Setpoint: Starting RPM
Group
Engine Params
Range [units]
5 ... 50 [%]
Related
All
applications
This setpoint defines the "firing" speed level as percent value of the nominal
Description
speed. If this level is exceeded the engine is considered as started. More
information is available in the
NT
InteliCompact
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
Engine start
chapter.