Setpoint: #SysPwrFactor
Group
Process Control
Range [units]
0.7 ... 1.0 [-]
Related
MINT
applications
Description
Required gen-set power factor when the group of gen-sets is running
parallel to the mains. The PF is regulated locally in each controller by PF
control regulation loop, VARsharing is not active.
Setpoint: Synchro Enable
Group
ProcessControl
Range [units]
NONE, FORWARD, REVERSE, BOTH [-]
Related
All
applications
Description
Enables or disables forward/reverse synchronization (according to SPtM /
MINT versions).
NONE
FORWARD
REVERSE
BOTH
Setpoint: PeakLevelStart
Group
Process Control
Range [units]
PeakLevelStop ... 32000 [kW]
Related
SPtM
applications
Description
Load consumption level the gen-set has to start at. Function is inactive when
PeakAutS/S Del
consumption of the Load exceeds the PeakLevelStart limit.
N
:
OTE
The actual setpoint units and range depend on setting of the Power format
(see the
N
:
OTE
It is necessary to use
current.
NT
InteliCompact
, SW version 2.1
InteliCompact-NT-2.1-Reference Guide.pdf, ©ComAp – May 2015
No synchronizing is enabled. (SPtM and MINT)
GCB synchronizing is enabled. (SPtM and MINT)
MCB synchronizing is enabled. (SPtM)
GCB and MCB synchronizing are enabled. (SPtM)
= OFF. Gen-set start is "PeakAutS/S Del" delayed after the
LiteEdit
manual).
IC-NT CT-BIO7
module and measure 1Ph Mains
162

Hide quick links:

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the InteliCompact NT and is the answer not in the manual?

Questions and answers

Sudarshan
March 11, 2025

Low backup batt

1 comments:
Mr. Anderson
March 11, 2025

The low backup battery warning on the ComAp InteliCompact NT indicates that the internal backup battery needs to be replaced. This alarm is evaluated continuously and applies to all applications. The backup battery has an approximate lifetime of 10 years, and when this alarm occurs, it is necessary to replace it with a CR1225 lithium battery.

This answer is automatically generated

Table of Contents

Save PDF