Electrostatic Discharge And Grounding Guide For Cisco Ncs; Step 1; Cisco Ncs 2000 Series Hardware Installation Guide - Cisco NCS 2006 Hardware Installation Manual

Ncs 2000 series
Table of Contents

Advertisement

Connecting Power and Ground
Connect the unit only to DC power source that complies with the safety extra-low voltage (SELV)
Warning
requirements in IEC 60950-1 based safety standards. Statement 1033
This product requires short-circuit (overcurrent) protection, to be provided as part of the building
Warning
installation. Install only in accordance with national and local wiring regulations. Statement 1045
This product relies on the building's installation for short-circuit (overcurrent) protection. Ensure
Warning
that the protective device is rated not greater than: 10A-20A, 100-240 VAC~. Statement 1005
A readily accessible two-poled disconnect device must be incorporated in the fixed wiring. Statement
Warning
1022
This unit might have more than one power supply connection. All connections must be removed to
Warning
de-energize the unit. Statement 1028
Always use the supplied ESD wristband when working with a powered NCS. For detailed instructions on
Caution
how to wear the ESD wristband, refer to the
2000 Series
Procedure

Step 1

Verify that the correct fuse panel is installed in the top mounting space:
• For a DC power supply, the fuse rating must not exceed 15A.
• For an AC power supply, the fuse rating must not exceed 10A, 15A, or 20A. For North America, the
branch circuit protection must be rated 20A. The overcurrent/short circuit protection must be in accordance
with local and national electrical codes.
Step 2
Depending on the shelf and the power module installed, complete the necessary task:
DLP-L49 Connecting Office Power (AC) to the NCS 2002 Shelf, on page 80
DLP-L50 Connecting Office Power (DC) to the NCS 2002 Shelf (ANSI Only), on page 83
DLP-L51 Connecting Office Power (DC) to the NCS 2002 Shelf (ETSI Only), on page 88
Step 3
Connect the office ground to the NCS 2002 shelf. For detailed instructions on grounding, refer to the
Electrostatic Discharge and Grounding Guide for Cisco NCS 2000 Series
Step 4
Complete
Step 5
Continue with the
.
DLP-L53 Turning On and Verifying DC Office Power on the NCS2002Shelf, on page
NTP-L35 Installing the Fan-Tray Assembly in the NCS 2002 Shelf, on page
NTP-L35 Installing the Power and Ground to the NCS 2002 Shelf

Electrostatic Discharge and Grounding Guide for Cisco NCS

Cisco NCS 2000 Series Hardware Installation Guide

.