Harmonic Filter Module Installation - YASKAWA D1000 Series Instruction Manual

Type cimr-du/power regenerative converter 200 v class, three-phase input: 5 to 130 kw/400 v class, three-phase input: 5 to 630 kw
Hide thumbs Also See for D1000 Series:
Table of Contents

Advertisement

2.2 Harmonic Filter Module Installation

2.2
Harmonic Filter Module Installation
◆ Installation Environment
Install the harmonic filter module in an environment matching the specifications in
performance life of the harmonic filter module.
Environment
Indoors
Installation Area
Install the converter in an environment that does not easily accessible such as control panel.
IP00/Open Type enclosure: -10°C to +50°C (14 °F to 122 °F)
Harmonic filter module reliability improves in environments without wide temperature fluctuations.
Ambient
When using the harmonic filter module in an enclosure panel, install a cooling fan or air conditioner in the area to ensure
Temperature
that the air temperature inside the enclosure does not exceed the specified levels.
Do not allow ice to develop on the harmonic filter module.
Humidity
95% RH or less and free of condensation
Storage
–20°C to +60°C (-4 °F to +140 °F)
Temperature
Install the harmonic filter module in an area free from:
• oil mist and dust
• metal shavings, oil, water, or other foreign materials
• radioactive materials
Surrounding Area
• combustible materials (e.g., wood)
• harmful gases and liquids
• excessive vibration
• chlorides
• direct sunlight.
Altitude
3000 m (9843 ft.) or lower
Vibration
2.0 m/s
NOTICE: Prevent foreign matter such as metal shavings and wire clippings from falling into the converter and harmonic filter module
during installation. Failure to comply could result in damage to the converter and the harmonic filter module. Place a temporary cover
over the top of the converter and the harmonic filter module during installation. Remove the temporary cover before converter and
harmonic filter module start-up, as the cover will reduce ventilation and cause the converter and the harmonic filter module to overheat.
◆ Installation Orientation and Spacing
Installation Orientation
Install the harmonic filter module on the floor with the faceplate facing forward.
Figure 2.9
38
Table 2.8 Installation Environment
2
(20 to 55 Hz)
A
A – Faceplate
Figure 2.10 Correct Installation Orientation
YASKAWA ELECTRIC TOEP C710656 07A YASKAWA Power Regenerative Converter - D1000 Instruction Manual
Table 2.8
Conditions
B
B – Top cover
to help prolong the optimum

Advertisement